GW EIP/ASCII...
58
PHOENIX CONTACT
3785_en_B
5.4.2
Status word
Table 5-13 shows the Identity object status word.
Table 5-13
Identity object status word
Status word
bit
Setting
Description
0
0
Ownership flag. Does not apply to the
GW EIP/ASCII....
1
0
Reserved
2
0
The GW EIP/ASCII... is operating on the default
configuration
1
The GW EIP/ASCII... has a configuration other than
the default configuration
3
0
Reserved
4-7
0101 (0x50)
Indicates that there is a major fault (either bit 10 or bit
11 is set)
0100 (0x40)
Indicates the stored configuration is invalid
0011 (0x30)
Indicates the system is operational and there are no
I/O (Class 1) connections
0110 (0x60)
Indicates the system is operational and there is at
least one active I/O (Class 1) connection
0000
Indicates the system is not operational. It may be in
any of the following states: system startup,
configuration in process, idle, or critical (major) fault
8
0
No recoverable minor fault. No error history entry
reported within the last ten seconds.
1
Recoverable minor fault. The GW EIP/ASCII...has
reported an error within the last ten seconds and a
major fault has not been detected.
9
1
Unrecoverable minor fault. Does not apply to the
GW EIP/ASCII....
10
0
No recoverable major fault
1
A major recoverable fault exists. This is a fault that the
GW EIP/ASCII... may be able to recover from by a
system reset. If the system does not recover
automatically, a system reset message or a power
cycle of the GW EIP/ASCII... may be required.
11
0
No major unrecoverable fault
1
A major unrecoverable fault has occurred in the
GW EIP/ASCII.... If the major fault is not corrected
with a system reset or a power cycle, contact Phoenix
Contact.
12-15
0
Reserved
Содержание 2702772
Страница 1: ...User manual UM EN GW EIP ASCII Protocol converter for ASCII to EtherNet IP...
Страница 6: ...GW EIP ASCII 4 PHOENIX CONTACT 3785_en_B...
Страница 14: ...GW EIP ASCII 12 PHOENIX CONTACT 3785_en_B...
Страница 52: ...GW EIP ASCII 50 PHOENIX CONTACT 3785_en_B...
Страница 82: ...GW EIP ASCII 80 PHOENIX CONTACT 3785_en_B...