Data message format
3785_en_B
PHOENIX CONTACT
53
Table 5-4
Serial port data transfer object instance attributes
Attribute ID
Name
Data type
Data value
Access
rule
1
Transmit (PLC to GW EIP/ASCII...) message data
Structure of:
Produced data
sequence number
UINT
0-65535 (FFFF
hex
)
Set/Get
Data length
UINT
1-440
Data array
Array of USINT
0-255
2
Receive (GW EIP/ASCII... to PLC) message data
Structure of:
Produced data
sequence number
UINT
0-65535 (FFFF
hex
)
Get
Data length
UINT
1-440
1
Data array
Array of USINT
0-255
3
Receive (GW EIP/ASCII... to PLC) produced data sequence number
Normally sent to the
PLC from the
GW EIP/ASCII... in
data transfer
UINT
0-65535 (FFFF
hex
)
Set/Get
5
Transmit (PLC to GW EIP/ASCII...) produced data sequence number
Normally sent to the
GW EIP/ASCII...
from the PLC in data
UINT
0-65535 (FFFF
hex
)
Set/Get
1
For polling transfer to PLC mode only
The maximum sized serial port message in the “Write-to-Tag” field when set to
Transfer
to PLC
is 1518 bytes.
Table 5-5
Serial port data transfer object common services
Service code
Implemented in
class
Implemented in
instance
Service name
0E
hex
Yes
Yes
Get_Attribute_Single
10
hex
No
Yes
Set_Attribute_Single
Содержание 2702772
Страница 1: ...User manual UM EN GW EIP ASCII Protocol converter for ASCII to EtherNet IP...
Страница 6: ...GW EIP ASCII 4 PHOENIX CONTACT 3785_en_B...
Страница 14: ...GW EIP ASCII 12 PHOENIX CONTACT 3785_en_B...
Страница 52: ...GW EIP ASCII 50 PHOENIX CONTACT 3785_en_B...
Страница 82: ...GW EIP ASCII 80 PHOENIX CONTACT 3785_en_B...