![Pepperl+Fuchs VBG-PB-K20-DMD-C1 Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/pepperl-fuchs/vbg-pb-k20-dmd-c1/vbg-pb-k20-dmd-c1_manual_1527750061.webp)
AS-i/PROFIBUS Gateway
PROFIBUS DP
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
59
9.1.3.3
AS-i 16-bit data
In addition to the access via the command interfaces, the 16-bit data for or by the
slaves with 16-bit value can by exchanged cyclically (profile 7.3., S-7.4, S-6.0, S-
7.5, S-7.A.8, S-7.A.9, S-7.A.A). Competing writing access attempts on analog out-
put data will not be blocked by each other. If analog data for a particular slave are
being transmitted both cyclically and acyclically with the command interface or via
DP V1 connections, the acyclically transmitted values will be overwritten by the cy-
clically transmitted values.
AS-i 16-bit data can be transmitted in a reserved data area. Therefore accessing
analog data is as easy as accessing digital data.
9.1.3.4
Command Interface
Only using the IDs of the process data field the AS-i/PROFIBUS gateway can be
used as M0 AS-i master. By using the command interface (see chapter 9.1.3) the
functions of a M3 master become available.
A-Slaves map the data on channels 1 and 2.
B-Slaves map the data on channels 3 and 4.
AS-i 16-bit data
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
slave 31-n/8, channel 1, high byte
2
slave 31-n/8, channel 1, low byte
3
slave 31-n/8, channel 2, high byte
4
slave 31-n/8, channel 2, low byte
…
…
n-3
slave 31, channel 3/slave 31B, channel 1, high byte
n-2
slave 31, channel 3/slave 31B, channel 1, low byte
n-1
slave 31, channel 4/slave 31B, channel 2, high byte
n
slave 31, channel 4/slave 31B, channel 2, low byte
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
command
2
T
circuit
3
request parameter byte 1
…
…
36
request parameter byte 34