AS-i/PROFIBUS GatewayAS-i/PROFIBUS-Gateway
Operating in Advanced Display Mode
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
23
The device starts in the classical mode (see chapter 7). Press OK to switch to the
advanced mode.
In the extended mode, the selection can be moved up and down with the arrow
buttons.
Pressing OK will switch you to the selected function or menu. Pressing ESC will
switch you back to the previous menu.
To edit data values highlight them with the selection bar, press OK, then change
them with the arrow-buttons and confirm with OK. The ESC-button cancels the
editing process.
All possible addresses are displayed one after the other from 1A to 31A and from
1B to 31B. Data for single slaves are displayed at the addresses 1A - 31A.
Classical (Traditional) mode does not guarantee any protection of the set-
tings at the device!
In the classical mode, it is possible to change settings while the device is in
operation. This can lead to failure of the plant (e. g. changing the address of
an AS-i slave).
The settings in the advanced mode are protected, as long as the PROFIBUS
Master Class 1 is running. That means that some states are indicated only.
Many operations (for example: "change address", "write parameter", "set
outputs", and so forth) are not possible via the display during the connection
with the control (active PROFIBUS masters Class 1Busconnection) for the
protection of the plant. Before these commands can be executed at the dis-
play, first the connection (PROFIBUS Master Class 1 connection) to the con-
trol must be deactivated.