AS-i/PROFIBUS GatewayAS-i/PROFIBUS-Gateway
Operating in Advanced Display Mode
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
43
7.8.2
LCS (list of slaves having caused a configuration error)
R E S E T
A P F -
I
1 A - x
2 A -
I 3 A -
4 A - x
I 5 A
This list shows for each single AS
-
i slave whether at least one configuration error
was caused by an enormous telegram transmission. This function is especially im-
portant if the configuration error only occurs short-time.
Empty field: No error
X:
AS
-
i slave caused a configuration error.
7.8.3
Fault detector
F A U LT D E T E C T O R
R E S E T
H I S T O R I C :
E F LT O V R V N O I S
A C T U A L :
E F LT O V R V N O I S
D U P A S I A D R :
0
I
3 1 B
H E L P :
E F LT E A R T H F A U LT
OVRV OVERVOLATAGE
N O I S N O I S E
D U P A S I A D R
D U P L I C AT E A S I
S L AV E A D D R E S S
The menu "Fault Detector" shows information about the AS-i detector and allows
deleting of the AS-i detector´s history. Furthermore a list of abbreviations in plain
language can be found is in the section "Help".
By selecting "Reset" the history of the AS-i detector can be deleted.
In the section "Historic" the appeared error messages of the AS-i detector are lis-
ted since the last "Reset".
In the section "Actual" the actual appeared error messages of the AS-i detector are
listed.
Following error messages are possible:
• Duplicate address (the 2 lowest slave addresses are displayed, at which a du-
plicate address exist).
• Earth faults
• Noise
• Overvoltage