10.5
Command Interface examples
You can find actual command interface examples in the download area of the
homepage.
10.5.1
Reading 16-bit input values
Command RD_7X_IN: Reading of 16-bit input values
.
PROFIBUS DP V0: cyclic data exchange
Used ID/module in the GSD file: 12-byte management
Meaning of the bytes:
The call of the command interaface has not been answered with the valid values
since the toggle bit has not been set.
Set of toggle bit:
Response (bei O
≡
1)
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
7D
16
2
T
result
3
0
1
2
3
4
5
6
7
…
…
6
24
25
26
27
28
29
30
31
Request: RD_7X_IN
Byte 1
50
hex
(RD_7X_IN)
Byte 2
00
hex
(master 1, single master)
Byte 3
1D
hex
(slave address 29)
Byte 4
00
hex
…
…
Byte 12
00
hex
Response
Byte 1
00
hex
(or old values)
Byte 2
00
hex
(or old values)
Byte 3
00
hex
(or old values)
Byte 4
00
hex
(or old values)
…
…
Byte 12
00
hex
(or old values)
Request
Byte 1
50
hex
Byte 2
80
hex
(toggle bit, result)
Byte 3
1D
hex
(slave address 29)