AS-Interface
Command Interface
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
126
No result because toggle bit = 0.
Set the toggle bit:
The master is now in configuration mode.
Result: See chapter 10.2.1 "Values for results".
2. Write single configuration to master
Writing a configuration of an AS-i slave to the master.
For example:
16-bit input 4 CH at address 4 (Slave datasheet)
ID: 3
hex
ID2:
E
hex
IO:
7
hex
ID1:
F
hex
Response
Byte 1
00
hex
(or old values)
Byte 2
00
hex
(or old values)
Byte 3
00
hex
(or old values)
Byte 4
00
hex
(or old values)
…
…
Byte 12
00
hex
(or old values)
Request: SET_OP_MODE
Byte 1
0C
hex
(SET_OP_MODE)
Byte 2
80
hex
(T = 1, master 1, single master)
Byte 3
01
hex
(= config mode)
Byte 4
00
hex
…
…
Byte 12
00
hex
Response
Byte 1
0C
hex
Byte 2
80
hex
(T = 1, result = 0)
Byte 3
00
hex
(or old values)
Byte 4
00
hex
(or old values)
…
…
Byte 12
00
hex
(or old values)