Appendix: Example for startup on a Siemens S7
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
157
As soon as the AS-i configuration error is cleared, the OB82 is invoked again. In
turn the diagnostic address of the AS-i/DP Gateway, here 1022, is entered as a
parameter and the event is declared as an outgoing event.
Entry of the error messages in the diagnostic buffer of the CPU and invoking of the
OB82 is a consequence of the set ExtDiag flag for an error in the AS-i/DP Gate-
way.
This can be prevented by turning off the ExtDiag flag in the PROFIBUS parame-
ters of the AS-i Gateway.
The errors can be responded to by the controller by querying the AS-i flag in the
input data. This means a configuration error is reported twice in a standard case:
Once via the AS-i flag Config Error and once via the ExtDiag flag in the PROFIBUS
telegram.
If for timing reasons an AS-i error must be responded to in a non-interrupt con-
trolled way, the message can be turned off using the ExtDiag flag. In this case it is
sufficient to check the AS-i flag Config Error in the program sequence.
The same applies to the other messages.
If the message for various error states of the AS-i Gateway is activated via the
PROFIBUS and if the data for the PROFIBUS diagnostic data are enabled, the SI-
EMENS function module SFC13 can be used to retrieve the PROFIBUS diagnostic