2
0
1
9
-1
0
82
ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for EtherCAT
Content of the Error Register
The symbol "-" can either be "0" or "1", if more than one error is active for each.
PDO 0x1A05, Diagnosis Register
Content of the Diagnosis Register
TwinCAT representation as UDINT: 0x Byte 4 - Byte 3 - Byte 2 - Byte 1
Legend
7.2.4
8DI8DO Modules, PDO Assignment
PDO for the ICE1-8DI8DO-G60L-V1D and ICE1-8DI8DO-G60L-C1-V1D
The PDOs 0x1A00 or 0x1A01 control the input data of the modules.
The PDOs 0x1600 or 0x1601 control the outputs of the modules.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Description
0
0
0
0
0
0
0
0
No error
-
0
0
0
0
-
1
1
Output overload,
MI-SCS
-
0
0
0
0
1
-
1
Voltage error, MI-
LVS
1
0
0
0
0
-
-
1
Force Mode
active, MI-FC
1
0
0
0
0
-
-
1
Additional device
diagnosis func-
tion, MI-IME
Table 7.29
PDO
Content
Index
Size
Index
Size
Type
Name
0x1A05
1
0x2001:01
4.0
UDINT
Diagnosis register
Table 7.30
Input
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 1
MI-IME
MI-FC
0
0
0
MI-SCS
0
MI-LVS
Byte 2
SCS-X5
SCS-X4
SCS-X3
SCS-X2
SCS-X4
SCS-X3
SCS-X2
SCS-X1
Byte 3
0
0
0
0
0
0
0
0
Byte 4
0
0
0
0
0
0
1
0
Table 7.31
MI-LVS
Module information byte
—
voltage for system/sensor performance low
MI-SCS
Module information byte
—
sensor short circuit at an M12 slot
MI-FC
Module information byte
—
Force Mode active
MI-IME
Module information byte
—
internal error
SCS-X1 ...
SCS-X8
Sensor short circuit at slot X1 to X8