![Pepperl+Fuchs ICE1 G60L-C1-V1D Series Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/pepperl-fuchs/ice1-g60l-c1-v1d-series/ice1-g60l-c1-v1d-series_manual_1527934027.webp)
ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for EtherNet/IP
2
0
1
9
-1
0
27
The following configuration parameters are available only for certain Ethernet IO module ver-
sions:
•
8DI8DO modules
•
Surveillance timeout: delay in output monitoring time on a channel
•
Fail-safe: initial state of a channel in the case of a fault
•
16DIO modules
•
Surveillance timeout: delay in output monitoring time on a channel
•
Fail-safe: initial state of a channel in the case of a fault
•
Process data direction
•
IO mapping: bit assignment for channels
QuickConnect Configuration
QuickConnect (QC) accelerates the start-up process of all Ethernet IO modules. Activating this
parameter enables network communication to start up particularly quickly.
If you activate QuickConnect, it takes no longer than 350 ms for the module to accept a TCP
connection after it is switched on. The controller subsequently establishes the connection. This
allows the module to achieve a start-up time of approximately 400 to 500 ms.
To use QC, the network must be arranged in a star or linear topology and the module must have
a static IP address. Ring topologies and DHCP/BOOTP are not supported. Please note that
there is no automatic check for duplicate IP addresses within the same network.
If QuickConnect is activated, the following parameters are fixed for the Ethernet interface of the
module:
•
100 Mbit/s transfer rate
•
Full duplex connection
•
Auto-negotiation and Auto-MDIX switched off
The following options are available for using QuickConnect:
•
Disabled (0) (default value)
•
Enabled (1)
General Settings Configuration
Whether these general parameters are displayed depends on the type of Ethernet IO module
used. Different parameters can be configured. Each bit in this bit field represents the state of a
parameter.
The following options are available for use with each individual parameter:
•
Disabled (0)
•
Enabled (1)
Note
A prerequisite for the use of QuickConnect is adherence to a strictly defined procedure. The
Ethernet IO modules must be notified before switching off (inhibit instruction) and before
switching on (uninhibit instruction).
A hard disconnection is not allowed during operation. Details of this procedure can be found in
document ENET-AT001C-ENP from Rockwell Automation
MSB
LSB
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
For 16DI 0r 16DIO modules with DI profiles
Word
0
RE
S
DO
R
DC
R
DC
L
RD
O
RU
L
WIL FM