![Pepperl+Fuchs ICE1 G60L-C1-V1D Series Скачать руководство пользователя страница 64](http://html1.mh-extra.com/html/pepperl-fuchs/ice1-g60l-c1-v1d-series/ice1-g60l-c1-v1d-series_manual_1527934064.webp)
2
0
1
9
-1
0
64
ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for PROFINET
The values refer to the following:
•
16-bit I/O DCU extension: bit states as input data for the decentralized control function
(DCU function)
•
INT I/O DCU extension: 8-word data types as input data for the decentralized control func-
tion (DCU function), e.g., for transmission of program parameters.
6.3.3
16DI Modules, Bit Assignment of Process Data
Input Data
The module provides 2 bytes of status information for the digital inputs. The bits are assigned
as follows:
The values refer to the following:
•
1A ... 8A: Actual status of input channel A (contact pin 4) for M12 connections 1 to 8.
•
1B ... 8B: Actual status of input channel B (contact pin 2) for M12 connections 1 to 8.
6.3.4
8DI/8DO Modules, Bit Assignment of Process Data
Input Data
This module provides two bytes of input data that depict the current status of the input and out-
put channels.
The values refer to the following:
•
1A ... 4A: Actual status of input channel A (contact pin 4) for M12 connections 1 to 4.
•
1B ... 4B: Actual status of input channel B (contact pin 2) for M12 connections 1 to 4.
•
5A ... 8A: Actual status of output channel A (contact pin 4) for M12 connections 5 to 8.
•
5B ... 8B: Actual status of output channel B (contact pin 2) for M12 connections 5 to 8.
Input
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte n
4B
4A
3B
3A
2B
2A
1B
1A
Byte n+1 8B
8A
7B
7A
6B
6A
5B
5A
Table 6.13
Note
So that a diagnosis can be done within the module, the actual output statuses at the
module
—
in addition to the actual input statuses
—
are reflected in the input data (output mirror).
Input
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte n
4B
4 A
3B
3 A
2B
2 A
1B
1 A
Byte n+1 8B
8 A
7B
7 A
6B
6 A
5B
5 A
Table 6.14