ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for EtherCAT
7
Commissioning for EtherCAT
7.1
Preparation
Downloading and Installing the ESI File
An ESI file (EtherCAT Slave Information file) is required to configure a module in the controller.
The ESI file supports all module variants.
You can find the relevant ESI file in the
Commissioning
section of the product detail page for
Use the hardware or network configuration tools from your controller manufacturer to install the
ESI file for the module variant used. For TwinCat
®
, you usually have to copy the ESI file to the
installation folder, for example:
C:\TwinCAT\3.1\Config\Io\EtherCAT
. After installation,
the modules are available in the hardware catalogs.
Reading MAC IDs
Each module has a unique MAC ID that is assigned by the manufacturer. The MAC ID cannot
be changed by the user. The assigned MAC ID is printed on the front side of the module.
This MAC ID has no function for EtherCAT. For EoE (Ethernet over EtherCAT), the I/O module
is assigned a virtual MAC ID.
7.2
Configuration
PDO Assignments
The module supports different PDO assignments for input and output data. There are assign-
ments for bit or byte access with or without diagnostic data that are associated with the input
data (TxPDO, I/O module to EtherCAT
®
controller).
You determine the data content by selecting the appropriate PDO.
The modules offer the following PDO assignments:
7.2.1
16DIO Modules, PDO Mapping
The 16DIO-variant Ethernet modules are universally applicable and provide a variety of profiles
for basic configuration. With these, you can preconfigure a 16DIO module as a 16DI, 16DO or
8DI/8DO module and e.g. replace another if necessary. Each I/O channel can be used as an
input or output for the 16DI/DO profile. If an I/O channel is used as an input, the PLC program-
mer should not set the corresponding output bit.
By using the preconfigured alternate profiles, the risk of incorrect configuration is reduced
through the use of profiles 16DI, 16DO or 8DI/8DO. In these profiles, the I/O channels are con-
figured as "input" or "output".
Ethernet IO modules of type ICE1-8DI8DO-G60L-C1-V1D ICE1-16DIO-G60L-C1-V1D have
the DCU function. For these, the process data is extended in both directions by 4 additional
bytes.
For this reason, each of the profiles supports flexible I/O bit mapping. Information on how to use
flexible I/O bit mapping can be found in the following chapter, "Device Parameters" in the sec-
tions "Configuration of I/O direction (for 16DIO modules with/without DCU)" and "I/O mapping
configuration (for 16DIO modules with/without DCU)"
Overview of the 16DIO Profiles in Byte Format
The following table provides an overview of the available I/O profiles and associated PDOs in
byte format