ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for EtherNet/IP
5.3
Bit Assignment of Process Data
Input and Output Data
Actual values are specified for the input data and target values are specified for output data.
Please note that the number of items of provider data (input data) is variable. It is dependent on
whether you have selected that the diagnostics data should be transferred. The modules pro-
vide one byte for slot diagnostics or channel diagnostics
—
the
module information byte
. The
diagnostics data supplements the standard process input data as additional bytes.
16DIO modules with decentralized control function
16DIO modules with decentralized control function (DCU) have an extended process data
range with an additional 18 bytes in both directions. These are appended to the output data,
module information byte or input data diagnoses. For further details on how to use the extended
process data ranges, see the chapter "decentralized control function.
”
5.3.1
16DIO Modules, Bit Assignment of Process Data
16-bit output data, default IO mapping (assembly ID 100)
16-bit input data with diagnosis, default IO mapping (assembly ID 101)
16-bit input data with diagnostic and padding byte, default IO mapping (assembly ID
108)
Note
So that a diagnosis can be done within the module, the actual output statuses at the
module
—
in addition to the actual input statuses
—
are reflected in the input data (output mirror).
INPUT
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
X4-B
X4-A
X3-B
X3-A
X2-B
X2-A
X1-B
X1-A
Byte 1
X8-B
X8-A
X7-B
X7-A
X6-B
X6-A
X5-B
X5-A
Table 5.36
INPUT
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
X4-B
X4-A
X3-B
X3-A
X2-B
X2-A
X1-B
X1-A
Byte 1
X8-B
X8-A
X7-B
X7-A
X6-B
X6-A
X5-B
X5-A
Byte 2
MI-IME
0
0
0
MI-SCA
MI-SCS
MI-LVA
MI-LVS
Byte 3
SCS-X8
SCS-X7
SCS-X6
SCS-X5
SCS-X4
SCS-X3
SCS-X2
SCS-X1
Byte 4
0
0
0
0
0
0
0
0
Byte 5
CE-X4B
CE-X4A
CE-X3B
CE-X3A
CE-X2B
CE-X2A
CE-X1B
CE-X1A
Byte 6
CE-X8B
CE-X8A
CE-X7B
CE-X7A
CE-X6B
CE-X6A
CE-X5B
CE-X5A
Table 5.37
INPUT
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
X4-B
X4-A
X3-B
X3-A
X2-B
X2-A
X1-B
X1-A
Byte 1
X8-B
X8-A
X7-B
X7-A
X6-B
X6-A
X5-B
X5-A
Byte 2
MI-IME
0
0
0
MI-SCA
MI-SCS
MI-LVA
MI-LVS
Byte 3
SCS-X8
SCS-X7
SCS-X6
SCS-X5
SCS-X4
SCS-X3
SCS-X2
SCS-X1
Byte 4
0
0
0
0
0
0
0
0
Byte 5
CE-X4B
CE-X4A
CE-X3B
CE-X3A
CE-X2B
CE-X2A
CE-X1B
CE-X1A
Byte 6
CE-X8B
CE-X8A
CE-X7B
CE-X7A
CE-X6B
CE-X6A
CE-X5B
CE-X5A