![Pepperl+Fuchs ICE1 G60L-C1-V1D Series Скачать руководство пользователя страница 118](http://html1.mh-extra.com/html/pepperl-fuchs/ice1-g60l-c1-v1d-series/ice1-g60l-c1-v1d-series_manual_1527934118.webp)
2
0
1
9
-1
0
118
ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
The Integrated Web Server
•
X1-A ... X8-A: Actual status of input/output channel A (contact pin 4) for M12 connections
1 to 8.
•
X1-B ... X8-B: Actual status of input/output channel B (contact pin 2) for M12 connections
1 to 8.
Description of the displayed byte values within the JSON object
The process data of the module is shown in decimal format in the JSON object. Consult the
respective bit numbering for the precise meaning of the displayed values:
For this process data, the bit status (0 or 1) is multiplied by the corresponding bit numbering.
The following examples demonstrate this logic:
•
Activated digital input at port X3-B: Byte 0 of the input data shows the value 32 as the port
status in bit 5 (1 [bit status] x 32 [value])
•
Activated digital output at port X8-A: Byte 1 of the output data shows the value 64 as the
port status in bit 6 (1 [bit status] x 64 [value])
If multiple bits are set simultaneously, their values are totaled according to their byte assign-
ment. The following example demonstrates this logic for the output data and input data.
Output data for byte 0 and byte 1:
•
Port X3-A, port X2-B, and port X2-A are activated outputs, which means that bits 4, 3, and
2 in byte 0 are each 1 x bit numbering.
The total value of byte 0 = 16 + 8 + 4 = 28
•
Port X8-A, port X6-B, and port X5-A are activated outputs, which means that bits 6, 3, and
0 in byte 1 are each 1 x bit numbering.
The total value of byte 1 = 64 + 8 + 1 = 73
Input data for byte 0 and byte 1:
Note
The bit assignment of the diagnostic data from byte 1 (diag
–
Byte 1) is arranged according to a
different logic, since a sensor short circuit can only result from an overload at pin 1. The table
below shows the corresponding bit assignment.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 1
X8
X7
X6
X5
X4
X3
X2
X1
Table 8.3
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Bit num-
bering
128
64
32
16
8
4
2
1
Byte 0
X4-B
X4-A
X3-B
X3-A
X2-B
X2-A
X1-B
X1-A
Byte 1
X8-B
X8-A
X7-B
X7-A
X6-B
X6-A
X5-B
X5-A
Table 8.4
Note
To enable internal module diagnosis, the actual output statuses at the module
—
in addition to
the actual input statuses
—
are reflected in the input data (output mirror). To receive the pure
input data, the values of the output data must therefore be subtracted from the total value of the
input data in the JSON object. ().