ICE1-*-G60L-V1D, ICE1-*-G60L-C1-V1D
Commissioning for PROFINET
1.
Select "Device View" (1) and the desired module (2) (in this example, slot 1 with a 16DIO
module).
2.
Then, in the "General" tab, select the "Module parameters" (3) area.
Figure 6.14
You can now carry out the desired parameter settings in the dialog (4).
Parameter Overview
The parameter groups are briefly described below.
•
Report Alarms
Enable/disable global PROFINET alarm messages.
•
Report Alarm U
L
Enable/disable PROFINET alarm reporting on absence of supply to actuator (U
L
). If the
global PROFINET alarm messages are disabled, this alarm will not be reported.
•
Report Alarm DO without U
L
Enable/disable PROFINET alarm reporting on absence of supply to actuator (U
L
) and
activation of an output. If the global PROFINET alarm messages are disabled, this alarm
will not be reported.
•
Force Mode
Allow/block use of Force Mode via the web server.
•
Web Interface
Allow/block use of the web server.
•
Decentralized control function DCU start-up
(only for C1 modules)
Disable/block decentralized control function or start DCU program.