Hardware Installation
2
02
0-
11
43
For the FDS/OPC integration, up to 125 DGW or 1 000 ADMs (whichever maximum is reached
first) are supported for a single FDS server installation. For the FOUNDATION Fieldbus integra
-
tion, this limit does not apply because every DGW is a single FF-H1 field device without any
connection to the other gateways.
Required Hardware Components
4.2.1
Installing the Diagnostic Bus
The maximum length of the diagnoastic bus channel is 30 m.
Installing the Diagnostic Bus
1.
In order to connect the diagnostic gateway to the FieldConnex
®
Power Hub, use a 4-line wire.
2.
In order to connect the Power Hubs with each other, use a 4-wire cable or the optional ACC-
MB-HDC link cable.
3.
Use shielded wires for the diagnostic bus in EMC-sensitive areas. Connect the cable shield to
the grounding terminal of the gateway motherboard.
4.
The principal way of connecting stand-alone kits to each other and to the diagnostic gateway is
shown in the figure below.
5.
The terminals used at the diagnostic gateway depends on the kit used.
KT-MB-GT2AD.FF:see chapter 3.3.1
KT-MB-GT2AD.FF.IO: see chapter 3.4.1
Hardware Component
Description
KT-MB-GT2AD.FF
or
KT-MB-GT2AD.FF.IO
Kit comprising the following hardware components:
•
HD2-GT-2AD.FF.IO: Diagnostic gateway
•
MB-FB-GT.AD.FF / MB-FB-GT.AD.FF.IO: Motherboard for
diagnostic gateway / I/O motherboard for diagnostic gate
-
way
KT-MB-DMA
Kit comprising the following hardware components:
•
HD2-DM-A: Advanced diagnostic module
•
MB-FB-DM: Stand-alone motherboard for advanced diag
-
nostic module
Seg4
Seg3
Seg2
Seg1
SEC
PWR
PRI
PWR
Fieldbus
Diagnostic
Module
Extended
Version
Seg4
Seg3
Seg2
Seg1
SEC
PWR
PRI
PWR
Fieldbus
Diagnostic
Module
Extended
Version
Seg4
Seg3
Seg2
Seg1
SEC
PWR
PRI
PWR
Fieldbus
Diagnostic
Module
Extended
Version
ACC-MB-HDC link cable
Diagnostic Gateway
Diagnostic Bus Line
Ethernet
Diagnostic Modules
Channel 1
Channel 2
+
-
+
-
Alarm
LAST
MOTHERBOARD
LINK
This is used to
maintain loop
continuity at the
last motherboard
Содержание HD2-DM-A
Страница 1: ... Advanced Diagnostics HD2 DM A KT MB DMA KT MB GT2AD FF KT MB GT2AD FF IO Manual ...
Страница 131: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 131 ...
Страница 133: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 133 3 Select Browse The Device Selection window appears ...
Страница 136: ...2020 11 136 Advanced Diagnostics FOUNDATION Fieldbus Integration ...