2
02
0-
11
142
Cabinet I/O
7.6.1
Configuring Typical Cabinet Management Applications Manually
Using Cooling Control
1.
Select an unused relay contact output and connect a cooling device (e.g., ventilator) to it.
2.
Select an unused on/off controller and configure it as follows:
Options: Not inverted
On level: Temperature level at which the output is supposed to be switched ON.
Off level: Temperature level at which the output is supposed to be switched OFF.
Input selection: Select the temperature input to be used as reference temperature.
3.
Configure the output source of the selected relay contact output to the selected on/off
controller.
4.
Configure measurement unit of selected temperature input.
Using Heater Control
1.
Select an unused relay output and connect a heater device to it.