Appendix
2
02
0-
11
149
8.2
HD2-GT-2AD.FF.IO FF Blocks
The column "Char." shows which characteristics or conditions are applicable to this parameter.
•
OOS (Out of Service): The parameter can be written only if the target mode of the block is
"Out of Service".
•
S (Static): During each writing process to a parameter of this type, the parameter ST_REV
is increased by 1.
•
W (Writeable): The parameter can be modified by the user.
Since all parameters can be read, this is not marked in a special way.
8.2.1
ADM_TB Transducer Block
Parameters
Active field devices
x
x
x
Unbalance
x
x
Communication errors statistic
x
x
x
Field device polarity
x
x
x
Signal level
x
x
x
Trunk surge protector alarm
x
Device coupler alarm
x
x
Values
MB* - Mother
-
board
MB-FB-DMA
DART
Parameter
Char.
Description
ST_REV
S
During each writing process to a parameter marked by "S" the
parameter ST_REV is increased by 1.
TAG_DESC
S, W
An additional description to the tag of the field device.
STRATEGY
S, W
The strategy field can be used to identify comprising blocks.
This data is not controlled or used by the block.
ALERT_KEY
S, W
Identification number of the plant component. This information
can be used by the control computer, e.g., to sort alarms. Valid
values are 1 ... 65536.
MODE_BLK
S, W
Displays the current, permitted standard mode and the target
mode of the block. The target mode can be set to the values
"Auto" or "Out of Service".
Default: Auto
BLOCK_ERR
•
Out of Service: The actual block mode is OOS.
•
Block configuration error: Check all segment expert sys
-
tem messages for information on configuration error cause.
•
Other: The status of any ADM segment is not "good", "no
error", "excellent" or "segment disabled".
UPDATE_EVT
This parameter is used to signal to the PCS that a parameter
marked with "S" was overwritten, provided the PCS supports
alarm messages.
BLOCK_ALM
This parameter is used to signal to the PCS diagnostic mes
-
sages displayed in BLOCK_ERR, provided the PCS supports
alarm messages.
XD_STATUS
Record
SYSTEM_STATUS
:
Status of the ADM system (bulk power supply voltage).
SEGMENT_*_STATUS
:
Summary value of segment quality.
Содержание HD2-DM-A
Страница 1: ... Advanced Diagnostics HD2 DM A KT MB DMA KT MB GT2AD FF KT MB GT2AD FF IO Manual ...
Страница 131: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 131 ...
Страница 133: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 133 3 Select Browse The Device Selection window appears ...
Страница 136: ...2020 11 136 Advanced Diagnostics FOUNDATION Fieldbus Integration ...