Cabinet I/O
•
High Maintenance Required: If the currently measured frequency value is higher than the
High-Maintenance–Required limit, the field diagnostics IO_TB–Maintenance–Required
condition is triggered.
•
Low Maintenance Required: Like High Maintenance Required, but for measured fre
-
quency lower than the Low–Maintenance–Required value.
•
Low Maintenance Required: Like High Maintenance Required, but for measured fre
-
quency lower than the Low–Maintenance–Required value.
•
Hysteresis: In order to avoid the flickering of diagnostics, a hysteresis value can be config
-
ured.
7.2.2
Binary Inputs
•
Lead breakage and short circuit detection can be enabled and disabled.
•
Invert: Invert binary input value.
•
Use fault state: If an error is detected, the input status remains "GOOD" instead of becom
-
ing "BAD". Depending on the setting of "Fault state to value", the input value remains on
the last "GOOD" value or changes to the fault state value.
•
Fault state to value: If enabled, the input value changes to the value of the "Fault state" bit
when an error is detected instead of remaining on the last "GOOD" value.
•
Fault state: Fault state value, used with "Fault state to value".
•
Field Diag Out Of Specification: If this option is set, a logical 1 at the binary input triggers
an IO_TB-Out-of-Specification condition.
•
Field Diag Maintenance Required: If this option is set, a logical 1 at the binary input trig
-
gers an IO_TB-Maintenance-Required condition.
7.2.3
Temperature/Binary Inputs
•
Lead breakage and short circuit detection can be enabled and disabled.
•
Use as binary input: Use input as binary input instead of temperature input.
The following settings are only used in binary mode:
•
Invert: Invert binary input value.
•
Use fault state: If an error is detected, the input status remains "GOOD" instead of becom
-
ing "BAD". Depending on the setting of "Fault state to value", the input value remains on
the last "GOOD" value or changes to the fault state value.
•
Fault state to value: If enabled, the input value changes to the value of the "Fault state" bit
when an error is detected instead of remaining on the last "GOOD" value.
•
Fault state: Fault state value, used with "Fault state to value".
•
Field Diag Out Of Specification: If this option is set, a logical 1 at the binary input triggers
an IO_TB-Out-of-Specification condition.
•
Field Diag Maintenance Required: If this option is set, a logical 1 at the binary input trig
-
gers an IO_TB-Maintenance-Required condition.
The following settings are only used in temperature mode:
•
High Out of Specification: If the currently measured temperature value is higher than
High-Out-of-Specification limit, the field diagnostics IO_TB-Out-of-Specification condition
is triggered.
•
High Maintenance Required: If the currently measured temperature value is higher than
High-Maintenance-Required limit, the field diagnostics IO_TB-Maintenance-Required
condition is triggered.
•
Low Maintenance Required: Like High Maintenance Required, but for measured tempera
-
ture lower than Low-Maintenance-Required value.
Содержание HD2-DM-A
Страница 1: ... Advanced Diagnostics HD2 DM A KT MB DMA KT MB GT2AD FF KT MB GT2AD FF IO Manual ...
Страница 131: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 131 ...
Страница 133: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 133 3 Select Browse The Device Selection window appears ...
Страница 136: ...2020 11 136 Advanced Diagnostics FOUNDATION Fieldbus Integration ...