2
02
0-
11
158
Appendix
HUMIDI
-
TY_IN
-
PUT_INT
Board humidity value and status
FREQ_IN
-
PUT_X (1-
2)
Frequency input X value and status
RELAY_OUT
-
PUT_X (1-
2)
Output value and status of relay output:
•
0: Relay is off (open)
•
1: Relay is on (closed)
BUZZER_OUT
PUT
Output value and status of buzzer:
•
0: Buzzer is off
•
1: Buzzer is active
COM
-
MON_ALARM_
OUTPUT
Output value and status of common alarm output. This is a fail
-
ure output, so
“
on
”
means
“
open
”
:
1. 0: Common alarm output is closed
2. 1: Common alarm output is open
ON_OFF_
-
CONT_X (1-
4)
Output value and status of on/off controller
FD_BINA
-
RY_OOS_MAP
W, S, OOS
When activated, a value of "1" of the corresponding binary
input triggers a field diagnostics IO_TB-Out-of-Specification
condition.
FD_BINA
-
RY_MR_MAP
W, S, OOS
When activated, a value of "1" of the corresponding binary
input triggers a field diagnostics IO_TB-Maintenance-
Required condition.
BINARY_IN
-
PUT_1_SET
-
TINGS/
BINARY_IN
-
PUT_2_SET
-
TINGS
Record, W, S,
OOS
TAG
Tag of the input
OPTIONS
•
Enable or disable lead breakage detection
•
Enable or disable short circuit detection
•
Use input as frequency input instead of binary input
•
Invert (binary mode only)
•
Use Fault state (binary mode only)
•
Fault state to value (binary mode only)
•
Fault state (binary mode only)
HI_HI_OOS
Field diagnostics High-Out-of-Specification frequency limit
(frequency mode)
HI_MR
Field diagnostics High-Maintenance-Required frequency limit
(frequency mode)
LO_MR
Field diagnostics Low-Maintenance-Required frequency limit
(frequency mode)
LO_LO_OOS
Field diagnostics Low-Out-of-Specification frequency limit (fre
-
quency mode)
HYSTERESIS
Diagnostics hysteresis in order to avoid alarm flickering (fre
-
quency mode).
Parameter
Char.
Description
Содержание HD2-DM-A
Страница 1: ... Advanced Diagnostics HD2 DM A KT MB DMA KT MB GT2AD FF KT MB GT2AD FF IO Manual ...
Страница 131: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 131 ...
Страница 133: ...Advanced Diagnostics FOUNDATION Fieldbus Integration 2020 11 133 3 Select Browse The Device Selection window appears ...
Страница 136: ...2020 11 136 Advanced Diagnostics FOUNDATION Fieldbus Integration ...