Drive Controlled Pump
Parker Hannifin Corporation
Hydraulics Group
DCP Manual innen A4 UK.indd 06.11.17
59
Manual
Technical data
Environmental details
Earthing/Safety Details
Operating Temperature
Operating temperature is defined as the surrounding air temperature of the drive, when the drive and
other equipment adjacent to it is operating at worst case conditions.
NORMAL DUTY
0°C to 40°C, derate up to a maximum of 50°C
HEAVY DUTY
0°C to 45°C, derate up to a maximum of 50°C
Output power is derated linearly at 2% per degree centigrade for temperature exceeding the maximum
rating for the drive.
Storage Temperature
-25°C to +55°C
Shipping Temperature
-25°C to +70 °C
Product Enclosure Rating
IP20 – remainder of surfaces (Europe)
UL (c-UL) Open Type (North America/Canada)
Cubicle Mounted
IP20
UL (c-UL) Open Type (North America/Canada)
Through-panel Mounted
IP20
UL (c-UL) Open Type (North America/Canada)
Altitude
If greater than 1000m above sea level, derate by 1% per 100m to a maximum of 2000m
Humidity
Maximum 85% relative humidity at 40°C non-condensing
Atmosphere
Non flammable, non corrosive and dust free
Climatic Conditions
Class 3k3, as defined by EN60721-3-3
Chemically Active Sub-
stances
For the standard product (which inherently includes our optimal level of conformal coating) compli-
ance with EN60721-3-3 is as follows –
a) Both classes 3C3 and 3C4 for hydrogen sulphide gas (H2S) at a gas concentration of 25ppm for
1200 hours.
b) Both classes 3C1 (rural) and 3C2 (urban) for all nine defined substances as defined in table 4.
Classes 3C1 and 3C2 are valid for both storage and transportation purposes.
Note - Product was tested and validated with a hydrogen sulphide environment of 25ppm for a conti-
nuous period of 1200 hours and validated throughout the test period without failure.
Vibration
Test Fc of EN60068-2-6
10Hz<=f<=57Hz sinusoidal 0.075mm amplitude
57Hz<=f<=150Hz sinusoidal 1g
10 sweep cycles per axis on each of three mutually perpendicular axis
Safety
Overvoltage Category
Overvoltage Category III (numeral defining an impulse withstand level)
Pollution Degree
Pollution Degree II (non-conductive pollution, except for temporary condensation) for control electro-
nics
Pollution Degree III (dirty air rating) for through-panel mounted parts
North America/Canada
Complies with the requirements of UL508C as an open-type drive.
Earthing
Permanent earthing is mandatory on all units.
· Use a copper protective earth conductor 10mm² minimum cross-section, or install a second con-
ductor in parallel with the protective conductor to a separate protective earth terminal
· he conductor itself must meet local requirements for a protective earth conductor
Input Supply Details
Drives without filters are suitable for earth referenced (TN) or non-earth referenced (IT) supplies.
(TN) and (IT)
The drive is only suitable for earth referenced supplies (TN) when fitted with an internal filter. External
filters are available for use on TN and IT (non-earth referenced) supplies.
Prospective Short Circuit Cur-
rent (PSCC)
Refer to the appropriate Electrical Ratings table.
Earth Leakage Current
>10mA (all models)