Drive Controlled Pump
Parker Hannifin Corporation
Hydraulics Group
DCP Manual innen A4 UK.indd 06.11.17
44
Manual
This parameter defines the settings of the pump(s).
Menu item
Setup::Application::Setup pump
PNO
1901
1904
1905
1906
Parameter name
Pump type
Double pump
Displacement pump1
Displacement pump2
Parameter
description
The pump type is defined by
the last 5 digits of the DCP or-
der code.
Single or Double pump
Displacement of pump 1
[ccm/rev]
Displacement of pump 2
[ccm/rev]
Function
By selecting the appropriate
type of pump, all relevant pa-
rameters such as displace-
ment, min. / max. speed, max.
pressure and number of pumps
(double pump (yes / no)) are
set automatically.
If the pump is not configured
via the DCP code, this pa-
rameter selects between sin-
gle or double pump. The DCP
code has to be set to default
(DCPxxxxxxxxxxxA0000).
If the pump is not configured
via the DCP code, this pa-
rameter sets the displace-
ment of pump 1. The DCP
code has to to be set to de-
fault (DCPxxxxxxxxxxxA0000).
If the pump is not configured
via the DCP code, this pa-
rameter sets the displace-
ment of pump 2. The DCP
code has to be set to default
(DCPxxxxxxxxxxxA0000).
Pump Settings
Menu item
Setup::Application::Setup pump
PNO
1908
1909
1912
1913
Parameter name
Pump speed min
Pump speed max
Max pressure pump 1
Max pressure pump 2
Parameter
description
Min. rotation speed of the
pumps [rpm]
Max. rotation speed of the
pumps [rpm]
Max. pressure of pump 1
[bar]
Max. pressure of pump 2
[bar]
Function
If the pump is not configured
via the DCP code, this param-
eter sets the min. speed of the
drive. If a double pump is se-
lected, the higher min. speed
of both pumps has to be se-
lected (entered). The DCP
code has to be set to default
(DCPxxxxxxxxxxxA0000).
If the pump is not configured
via the DCP code, this param-
eter sets the max. speed of the
drive. If a double pump is se-
lected, the lower max. speed
of both pumps has to be se-
lected (entered). The DCP
code has to be set to default
(DCPxxxxxxxxxxxA0000).
If the pump is not configured
via the DCP code, this param-
eter sets the max. pressure of
pump 1.
If a double pump is installed,
the max. pressure is a function
of the pump selection.
(e.g.: max. pressure of pump
1 = 300 Bar /// max. pressure
of pump 2 = 170 Bar. If both
pumps are used, the max. pres-
sure is p = 170 Bar. If the sec-
ond pump is deactivated (e.g.
via the digital input), the max.
pressure is set to p = 300 Bar.)
The DCP code needs to be
set to default (DCPxxxxxxx
xxxxA0000).
If the pump is not configured
via the DCP code, this param-
eter sets the max. pressure of
pump 2.
If a double pump is installed,
the max. pressure is a function
of the pump selection.
(e.g.: max. pressure of pump
1 = 300 Bar /// max. pressure
of pump 2 = 170 Bar. If both
pumps are used, the max.
pressure is p = 170 Bar. If the
second pump is deactivated
(e.g. via the digital input), the
max. pressure is set to p =
300 Bar.)
This parameter selects the application. Depending on the selected application, the control strategy and terminal usage change.
Menu item
Setup::Application::App Selection
PNO
1900
Parameter Descriptions
Selected Application
Selection of Drive Controlled Pump modes:
0: Q CONTROL
Flow control
1: p CONTROL
Pressure control
2: p/Q CONTROL
Flow control with mit combined pressure control
3: LS CONTROL
Load sensing
4: ACCUMULATOR CONTROL
Accumulator function with pressure sensor or 2-level pressure switch
Description
The selected application can only be changed when the drive is in configuration mode. The
menus and parameters, viewed on the GKP (graphical keypad) depend on the application.
Unused parameters are hidden.
Parameter description
App Selection