9-16
Function Parameters
AC10 Inverter
F209 Selecting the mode of
stopping the motor
Setting range:
0: stop by deceleration time;
1: free stop(coast stop)
Mfr’s value: 0
When the stop signal is input, stopping mode is set by this function code:
F209=0: stop by deceleration time
Inverter will decrease output frequency according to setting acceleration/deceleration curve and
decelerating time, after frequency decreases to 0, inverter will stop.
F209=1: free stop
After stop command is valid, inverter will stop output. Motor will free stop by mechanical inertia.
F210 Frequency display
accuracy
Setting range:
0.01
~
2.00
Mfr’s value: 0.01
Under keypad speed control or terminal UP/DOWN speed control, frequency display accuracy
is set by this function code and the range is from 0.01 to 2.00. For example, when F210=0.5,
▲
/
▼
terminal is pressed at one time, frequency will increase or decrease by 0.5Hz
F211 Speed of digital control
Setting range:
0.01
~
100.0Hz/S
Mfr’s value: 5.00
When UP/DOWN terminal is pressed, frequency will change at the setting rate. The Mfr’s value
is 5.00Hz/s.
F212 Direction memory
Setting range:
0: Invalid
1: Valid
Mfr’s value: 0
This function is valid when three-line operation mode 1(F208=3) is valid.
When F212=0
,
after inverter is stopped, reset and repowered on, the running direction is not
memorized.
When F212=1
,
after inverter is stopped, reset and repowered on, if inverter starts running but
no direction signal, inverter will run according the memory direction.
F213 Auto-starting after
repowered on
Setting range:
0: invalid;
1: valid
Mfr’s value: 0
F214 Auto-starting after reset
Setting range:
0: invalid;
1: valid
Mfr’s value: 0
Whether or not to start automatically after repowered on is set by F213
F213=1, Auto-starting after repowered on is valid. When inverter is power off and then powered
on again, it will run automatically after the time set by F215 and according to the running mode
before power-down. If F220=0 frequency memory after power-down is not valid, inverter will run
by the setting value of F113.
F213=0, after repower-on, inverter will not run automatically unless running command is given
to inverter.
Whether or not to start automatically after fault resetting is set by F214
When F214=1, if fault occurs, inverter will reset automatically after delay time for fault reset
(F217). After resetting, inverter will run automatically after the auto-starting delay time (F215).
If frequency memory after power-down (F220) is valid, inverter will run at the speed before