12-8
Modbus Communication
AC10 Inverter
12.7 Function Codes Related to Communication
Function Code Function Definition Setting Rang
Mfr’s
Value
F200
Source of start
command
0: Keypad command;
1: Terminal command;
2: Keypad
+
Terminal;
3: MODBUS;
4: Keypad
+
Terminal
+
MODBUS
4
F201
Source of stop
command
0: Keypad command;
1: Terminal command;
2: Keypad
+
Terminal;
3: MODBUS;
4: Keypad
+
Terminal
+
MODBUS
4
F203
Main frequency source
X
0: Digital setting memory;
1: External analog AI1;
2: External analog AI2;
3: Pulse input given;
4: Stage speed control;
0
F900
Inverter Address
1~255 : single inverter address
0: Broadcast address
1
F901
Modbus Mode
Selection
1: ASCII mode
2: RTU mode
1
F903
Parity Check
0: Invalid
1: Odd
2: Even
0
F904
Baud Rate(bps)
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
3
Set functions code related to communication consonant with the PLC/PC communication
parameters, when inverter communicates with PLC/PC.