15-6
Parameter Reference
AC10 Inverter
Multifunctional Input and Output Terminals: F300-F330
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
F300
Relay token output
0: no function;
1: inverter fault protection;
2: over latent frequency 1;
3: over latent frequency 2;
4: free stop;
5: in running status 1;
6: DC braking;
7: accel/decel time switchover;
8-9: Reserved;
10: inverter overload pre-alarm;
11: motor overload pre-alarm;
12: stalling;
13: Inverter is ready to run
14: in running status 2;
15: frequency arrival output;
16: overheat pre-alarm;
17: over latent current output
18: Analog line disconnection
protection
19: Reserved;
20: Zero current detecting output
21: DO1 controlled by PC/PLC
22: Reserved;
23: TA, TC fault relay output
controlled by PC/PLC
24: Watchdog
25-39: Reserved;
40: High-frequency performance
switchover
1
√
F301
DO1 token output
14
√
5
F303-
F306
Reserved
F307
Characteristic frequency 1
F112
~
F111
10.00
√
F308
Characteristic frequency 2
F112
~
F111
50.00
√
F309
Characteristic frequency width (%)
0
~
100
50
√
F310
Characteristic current (A)
0
~
1000
Rated
current
√
F311
Characteristic current width (%)
0
~
100
10
√
F312
Frequency arrival threshold (Hz)
0.00
~
5.00
0.00
√
F313-
F315
Reserved