![Parker 10G-42-0065-BF Скачать руководство пользователя страница 129](http://html.mh-extra.com/html/parker/10g-42-0065-bf/10g-42-0065-bf_product-manual_755620129.webp)
Parameter Reference
15-3
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value Change
F140
User-defined Frequency Point 1
0
~
F142
1.00
╳
F141
User-defined voltage point 1
0
~
100
%
4
╳
F142
User-defined frequency point 2
F140
~
F144
5.00
╳
F143
User-defined voltage point 2
0
~
100
%
13
╳
F144
User-defined frequency point 3
F142
~
F146
10.00
╳
F145
User-defined voltage point 3
0
~
100
%
24
╳
F146
User-defined frequency point 4
F144
~
F148
20.00
╳
F147
User-defined voltage point 4
0
~
100
%
45
╳
F148
User-defined frequency point 5
F146
~
F150
30.00
╳
F149
User-defined voltage point 5
0
~
100
%
63
╳
F150
User-defined frequency point 6
F148
~
F118
40.00
╳
F151
User-defined voltage point 6
0
~
100
%
81
╳
F152
Output voltage corresponding to turnover
frequency
10
~
100
%
100
╳
F153
Carrier frequency setting
subject to inverter model
subject to
inverter
model
╳
F154
Automatic voltage rectification
Setting range:
0: Invalid 1: Valid
2:Invalid during deceleration
process
0
╳
F155
Digital secondary frequency setting
0
~
F111
0
╳
F156
Digital secondary frequency polarity setting
0~1
0
╳
F157
Reading secondary frequency
△
F158
Reading secondary frequency polarity
△
F159
Random carrier-wave frequency selection
0: Control speed normally;
1: Random carrier-wave
frequency
1
F160
Reverting to manufacturer values
0: Not reverting to
manufacturer values;
1: Reverting to manufacturer
values
0
╳
TC-Hydraulik - R
ü
sdorfer Str. 8 - 25746 Heide - Lars Lornsen - T: +49 481 909 - 34 - [email protected] - www.tc-hydraulik.de