15-4
Parameter Reference
AC10 Inverter
Running control mode: F200-F230
Function
Code
Function Definition
Setting Range
Mfr’s Value
Change
F200
Source of start command
0: Keypad command;
1: Terminal command;
2: Keypad
+
Terminal;
3:MODBUS;
4: Keypad
+
Terminal
+
MODBUS
4
╳
F201
Source of stop command
0: Keypad command;
1: Terminal command;
2: Keypad
+
Terminal;
3:MODBUS;
4: Keypad
+
Terminal
+
MODBUS
4
╳
F202
Mode of direction setting
0: Forward running locking;
1: Reverse running locking;
2: Terminal setting
3: Keypad
0
╳
F203
Main frequency source X
0: Digital setting memory;
1: External analog AI1;
2: External analog AI2;
3: Reserved;
4: Stage speed control;
5: No memory by digital setting;
6: Reserved;;
7: Reserved;
8: Reserved;
9: PID adjusting; 10: MODBUS
0
╳
F204
Secondary frequency source Y
0: Digital setting memory;
1: External analog AI1;
2: External analog AI2;
3: Reserved;;
4: Stage speed control;
5: PID adjusting;
6: Reserved;;
0
╳
F205
Reference for selecting secondary frequency
source Y range
0: Relative to max frequency;
1: Relative to main frequency X
0
╳
F206
Secondary frequency Y range
0
~
100
%
100
╳
F207
Frequency source selecting
0: X; 1: X+Y;
2: X or Y (terminal switchover);
3: X or X+Y (terminal switchover);
4: Combination of stage speed
and analog 5: X-Y
6: Reserved;
0
╳