15-16
Parameter Reference
AC10 Inverter
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
FA02
PID feedback signal source
1: AI1 2: AI2
0
√
FA03
Max limit of PID adjusting (%)
FA04
~
100.0
10.00
√
FA04
Digital setting value of PID adjusting (%)
FA05
~
FA03
50.0
√
FA05
Min limit of PID adjusting (%)
0.0
~
FA04
0.0
√
FA06
PID polarity
0: Positive feedback
1: Negative feedback
1
╳
FA07
Sleep function selection
0: Valid 1: Invalid
0
╳
FA09
Min frequency of PID adjusting (Hz)
Max(F112, 0.1)~F111
5.00
√
FA10
Sleep delay time (S)
0~500.0
15.0
√
FA11
Wake delay time (S)
0.0~3000
3.0
√
FA18
Whether PID adjusting target is changed 0: Invalid 1: Valid
1
√
FA19
Proportion Gain P
0.00~10.00
0.3
√
FA20
Integration time I (S)
0.0~100.0S
0.3
√
FA21
Differential time D (S)
0.00~10.00
0.0
√
FA22
PID sampling period (S)
0.1
~
10.0s
0.1
√
FA29
PID dead time (%)
0.0
~
10.0
2.0
√
FA58
Fire pressure given value (%)
0.0~100.0
80.0
√
FA59
Emergency fire mode
0: Invalid
1: Emergency fire mode 1
2: Emergency fire mode 2
0
√
FA60
Running frequency of emergency fire
F112~F111
50.0
√
FA61
Reserved
FA62
When emergency fire control terminal is
invalid
0: inverter cannot be stopped
manually
1: inverter can be stopped manually
0
×
FA63-
FA80
Reserved
Torque control parameters: FC00-FC40
Function
Code
Function
Definition
Setting Range
Mfr’s Value
Change
FC00
Speed/torque control selection
0
:
Speed control
1
:
Torque control
2
:
Terminal switchover
0
√
FC01
Delay time of torque/speed control
switchover
(
S
)
0.0
~
1.0
0.1
╳
FC02
Torque accel/decel time (S)
0.1
~
100.0
1
√
FC03-
FC05
Reserved
FC06
Torque reference source
0: Digital given (FC09)
1: Analog input AI1
0
╳