Digiplex/DigiplexNE LCD Keypad 29
n
6.4.2 D
OOR
L
EFT
O
PEN
I
NTERVAL
B
EFORE
A
CCESS
A
LARM
S
ECTION
[010]
The Door Left Open Interval is the time that a door can remain
open after an Access Granted or a Request for Exit without
generating an Access Alarm. Enter any value between 001
and 255 to determine the number of seconds the door may
remain open before the Access Alarm is triggered. Default =
60 seconds.
6.4.3 D
OOR
L
EFT
O
PEN
P
RE
-A
LARM
S
ECTION
[004]: O
PTION
[3]
If an Access Control door is programmed with a Door Left
Open Interval (see section 6.4.2 above), the Pre-Alarm will
cause the reader to beep a certain time before the end of the
Door Left Open Interval to alert users that the Access Control
door was left open and will generate an Access Alarm if it is
not closed. The Pre-Alarm beeps slower than the Door Left
Open Alarm (about twice every second). Program the Pre-
Alarm timer in section [011].
Option [3] OFF= The Pre-Alarm will not be generated.
Option [3] ON = Pre-Alarm is enabled (default).
6.4.4 D
OOR
L
EFT
O
PEN
P
RE
-A
LARM
T
IMER
S
ECTION
[011]
This timer will trigger the Door Left Open Pre-Alarm before the
end of the Door Left Open Interval (see section 6.4.3 above).
For example, if 60 seconds is programmed in section [010] and
15 seconds is programmed in section [011], then 60 minus 15 is
45. Therefore, the reader will start beeping after the door has
been open for 45 seconds. Enter any value between 001 and
255 to determine the seconds before the expiry of the Door Left
Open Interval that the reader will beep. Default = 15 seconds.
Содержание DGP2-641
Страница 1: ...LCD Access Control LCD Keypad V1 0 DGP2 641 DGP2 641AC Reference and Installation Manual...
Страница 10: ...8 Reference Installation Manual Figure 1 Connecting the Keypad and Keypad Zone...
Страница 12: ...10 Reference Installation Manual Figure 4 Access Control Connections DGP2 641AC...
Страница 13: ...Digiplex DigiplexNE LCD Keypad 11n Figure 5 Connecting a Shielded Routing Cable...
Страница 38: ...36 Reference Installation Manual Table 2 Special Characters Catalog...
Страница 43: ......
Страница 44: ...PRINTED IN CANADA 04 2002 DGP2641 EI07...