30 Reference & Installation Manual
Figure 7: Pre-Alarm example
6.4.5 D
OOR
L
EFT
O
PEN
A
LARM
F
EEDBACK
S
ECTION
[004]: O
PTIONS
[5]
AND
[6]
An Access Control door is programmed with a Door Left Open
Interval (see section 6.4.2 on page 29). Once this interval has
expired, the Door Left Open Alarm can be either audible or
silent and will either beep as long as the Access Alarm is
occurring or follow the Beep Timer in section [012]. The sound
of the Door Left Open Alarm resembles the rapid beep
generated during the last ten seconds of the Exit Delay. When
the door is closed during an Access Alarm, the Door Left Open
Restore event can be logged in the Event Buffer.
Option [5] OFF= The Door Left Open Alarm is silent.
Option [5] ON = The Door Left Open Alarm is audible
(default).
If option [5] is enabled:
Option [6] OFF= beep as long as the Door Left Open Alarm is
occurring (default).
Option [6] ON = Door Left Open Alarm follows Beep Timer
(section [012]).