69
Swimming pool only
Thermistor
Pump
Swimming pool
Heat EXT
Indoor
Outdoor
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 1 Zone system
Zone :Swimming pool
T
This is an application that connects to the swimming pool only.
Connects pool heat exchanger directly to indoor unit without using buffer tank.
Install pool pump and pool sensor (specified by Panasonic) at secondary side of the pool heat exchanger.
Remove remote controller from indoor unit and install in room where floor heating is installed.
Temperature of swimming pool can be set independently.
This system requires the optional PCB (CZ-NS4P).
In this application, cooling mode cannot be selected. (not display on remote controller)
Simple 2 zone (Floor h Radiator)
Thermistor 2
Thermistor 1
Pump 2
Mixing valve
Indoor
Outdoor
Radiator
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1 :Sensor
Water temperature
Zone 2 :Sensor
Room
Water temperature
Operation setup
Heat
T for heating ON – 1°C
Cool
T for cooling ON – 1°C
This is an example of simple 2 zone control without using buffer tank.
Built-in pump from indoor unit served as a pump in zone 1.
Install mixing valve, pump and thermistor (specified by Panasonic) on zone 2 circuit.
Please be sure to assign high temperature side to zone 1 as temperature of zone 1 cannot be adjusted.
Zone 1 thermistor is required to display temperature of zone 1 on remote controller.
Circulation water temperature of both circuits can be set independently.
(However, temperature of high temperature side and low temperature side cannot be reversed)
This system requires the optional PCB (CZ-NS4P).
(CAUTION)
Thermistor 1 does not affect operation directly. But error happens if it is not installed.
Please adjust flow rate of zone 1 and zone 2 to be in balance. If it is not adjusted correctly, it may affects the
performance.
(If zone 2 pump flow rate is too high, there is possibility that no hot water flowing to zone 1.)
Flow rate can be confirmed by “Actuator Check” from maintenance menu.