99
Maximum/minimum regulation of Target Water Temperature.
Heating
Cooling
Max 55°C 20°C
Min 20°C 5°C
Compensation Type: (Operation under Heat Mode and Cool Mode)
-
The set temperature defines the parameters for the ambient (Outdoor temperature) dependent operation of
the unit. The water temperature is determined automatically depending on the outdoor temperature. Default
setting is the colder outdoor temperature will result in warmer water and vice versa. The user has the
possibility to shift up and shift down the target water by remote control setting.
OD
(LO)
= Setting Of LOW Outdoor Ambient Temperature.
A
W
(LO)
W
(HI)
OD
(LO)
OD
(HI)
Outdoor
Ambient
OD
(HI)
= Setting Of HIGH Outdoor Ambient Temperature.
W
(LO)
= Setting Of Water Temperature at LOW OD Ambient.
W
(HI)
= Setting Of Water Temperature at HIGH OD Ambient.
-
Outdoor ambient is updated every 30 minutes when operation ON.
-
Setting water outlet temperature always follow W
(LO)
or W
(HI)
whenever is higher if outdoor ambient sensor or
indoor comminication error happen.
However, when powerful mode is requested by remote control during heating mode, the higher value of HLo or Whi
will be used for A calculation.
*There are 2 compensation curves (for heating and cooling). During heating mode, the heating curve is used and
during cooling mode, the cooling curve is use.
-
Compensation curve set shift value:
Tw
Tw_Hi
Tw_Lo
To_Hi
To
Shift value
+ 5
± 5
- 5
To_Lo