90
11.5 Outdoor Unit
11.5.1 Select the Best Location
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
Avoid installations in areas where the ambient temperature may drop below -20
°
C for UD models and -28
°
C for
UX models.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If outdoor unit installed near sea, region with high content of sulphur or oily location (e.g. machinary oil, etc), it
lifespan maybe shorten.
When installing the product in a place where it will be affected by typhoon or strong wind such as wind blowing
between buildings, including the rooftop of a building and a place where there is no building in surroundings, fix
the product with an overturn prevention wire, etc. (Overturn prevention fitting model number: K-KYZP15C)
If piping length is over 10 m, additional refrigerant should be added as shown in the table.
Piping size
Rated Length (m)
Model
Gas Liquid
For Heat
Pump Indoor
Unit
For
Hydromodule
+ Tank
Max.
Elevation
(m)
Min. Piping
Length
(m)
Max. Piping
Length
(m)
Additional
Refrigerant
(g/m)
UX09*E5*, UX12*E5*,
UD12*E5*, UD16*E5*,
UX09*E8*, UX12*E8*,
UX16*E8*, UD09*E8*,
UD12*E8*, UD16*E8*
ø15.88 mm (5/8") Ø9.52 mm (3/8")
7
5
20
3
30
50
Example:
If piping length is 30 m, the quantity of additional refrigerant should be 1000g. [(30-10)m × 50 g/m = 1000g]
GWP (R410A) = 2088