91
11.5.2 Install The Outdoor Unit
11.5.2.1 Installation
Diagram
It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation,
please consult authorized dealer/specialist.
This illustration is for explanation purposes only.
Vinyl tape (Wide)
Saddle
Indoor/Outdoor connecting cable
- For UX09*E5*, UX12*E5*, UD12*E5*, UD16*E5* use 4-CORE WIRE
min 4.0mm
2
or 6.0mm
2
- For UX09*E8*, UX12*E8*, UX16*E8*, UD0 9*E8*, UD12*E8*,
UD16*E8* use 6-CORE WIRE min 1.5mm
2
Type designation 60245 IEC 57 or heavier cord
ø15.88mm (5/8") Gas refrigerant piping
ø9.52mm (3/8") Liquid refrigerant piping
100m
m
or mo
re
10
00
mm
or
m
or
e
10
0m
m
or
m
or
e
300m
m
or m
ore
[
]
Check that the cables do not
touch the compressor, etc.
F
E
B
A
C
D
(Anchor pitch)
(A
nc
hor
pi
tc
h)
Model
A B C D E F
UX09*E5*,UX12*E5*,
UD12*E5*,UD16*E5*,
UX09*E8*,UX12*E8*,
UX16*E8*,UD09*E8*,
UD12*E8*,UD16*E8*
620 140 15 355 450 44
(Unit : mm)
After selecting the best location, start installation according to Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø10 mm).
2. When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly
with bolt or nails.
11.5.2.2 Disposal of Outdoor Unit Drain Water
When a Drain elbow
1
is used, please ensure to follow below:
-
the unit should be placed on a stand which is taller than 50 mm.
-
cover the ø20 mm holes with Rubber cap
2
(refer to illustration below).
-
use a tray (field supply) when necessary to dispose the outdoor unit drain water.
If the unit is used in an area where temperature falls below 0°C for 2 or 3 consecutive days, it is recommended
not to use the Drain elbow
1
and Rubber cap
2
, for the drain water freezes and the fan will not rotate.
Rubber cap
x 8
Drain elbow 1
2