16.5.7 Abnormal Swimming Pool Sensor (H31)
Malfunction Caused:
1 Faulty
connector
connection.
2 Faulty swimming pool sensor.
3 Faulty indoor sub PCB.
Abnormality Judgment:
Continue for 5 seconds.
YES
Correct connection
●
Change swimming pool sensor
NO
YES
Measure sensor resistance match swimming pool sensor
characteristic?
●
Correct sensor connection
NO
H31 happens check connector sensor at CN204 connection
normal?
Abnormal swimming pool sensor
Change Indoor sub PCB
Troubleshooting:
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Caution