71
Buffer tank + Solar
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Buffer Tank connection - Yes
T for buffer tank
Solar connection - Yes
Buffer tank
T turn ON
T turn OFF
Antifreeze
Hi limit
Solar thermistor
Thermistor
Solar pump
Mixing valve
Floor heating
Pump
Buffer tank
Outdoor
Indoor
This is an application that connects the buffer tank to the indoor unit before connecting to the solar water heater to
heat up the tank.
Buffer tank’s temperature is detected by buffer tank thermistor (specified by Panasonic).
Solar panel’s temperature is detected by solar thermistor (specified by Panasonic).
Buffer tank shall use tank with built-in solar heat exchange coil independently.
During winter season, solar pump for circuit protection will be activated continuously. If does not want to activate the
solar pump operation, please use glycol and set the anti-freezing operation start temperature to -20°C.
Heat accumulation operates automatically by comparing the temperature of tank thermistor and solar thermistor.
This system requires optional PCB (CZ-NS4P).
Boiler connection
Thermistor
Boiler
Mixing
valve
Floor heating
Pump
Buffer tank
Outdoor
Indoor
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Bivalent - Yes
Turn ON : outdoor temp
Control pattern
This is an application that connects the boiler to the indoor unit, to compensate for insufficient capacity by operate
boiler when outdoor temperature drops & heat pump capacity is insufficient.
Boiler is connected parallel with heat pump against heating circuit.
There are 3 modes selectable by remote controller for boiler connection.
Besides that, an application that connects to the DHW tank’s circuit to heat up tank’s hot water is also possible.
(Operation setting of boiler shall be responsible by installer.)
This system requires optional PCB (CZ-NS4P).
Depending on the settings of the boiler, it is recommended to install buffer tank as temperature of circulating water
may get higher. (It must connect to buffer tank especially when selecting Advanced Parallel setting.)
WARNING
Panasonic is NOT responsible for incorrect or unsafe situation of the boiler system.
CAUTION
Make sure the boiler and its integration in the system complies with applicable legislation.
Make sure the return water temperature from the heating circuit to the indoor unit does NOT exceed 55°C.
Boiler is turned off by safety control when the water temperature of the heating circuit exceed 85°C.