68
How to Use the Front Panel and Console
Display of the Factor of No-Motor Running
Displays the factor of no-motor running in number.
.......Position control
....... Velocity control
.......Torque control
....... Full-closed control
Control mode
• Explanation of factor No.
Factor
No.
flashing
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
all
all
all
all
all
all
P,S,F
P,F
P,F
P,F
S,T
S
S
T
T
all
Occurrence of
error/alarm
No particular factor
Main power shutoff
No entry of
SRV-ON input
Over-travel
inhibition input
is valid
Torque limit setup
is small
Analog torque
limit input is valid.
INH input is valid.
Command pulse
input frequency
is low.
CL input is valid.
ZEROSPD input
is valid.
External speed
command is small.
Internal speed
command is 0.
Torque command
is small.
Speed limit is
small.
Other factor
<Note>
* Motor might run even though the other number than 0 is displayed.
Factor
Content
Control
mode
Factor No.
An error is occurring, and an alarm is triggered.
No factor is detected for No-motor run.
The motor runs in normal case.
The main power of the driver is not turned on.
The Servo-ON input (SRV-ON) is not connected to COM–.
While Pr04 is 0 (Run-inhibition input is valid),
• CCW over-travel inhibition input (CCWL) is open and speed command is CCW direction.
• CW over-travel inhibition input (CWL) is open and speed command is CW direction.
Either one of the valid torque limit setup value of Pr5E (1st) or Pr5F (2nd) is set to 5% or
lower than the rating.
While Pr03 is 0 (analog torque limit input accepted),
• CCW analog torque limit input (CCWTL) is negative voltage and speed command is CCW
direction.
• CW analog torque limit input (CWTL) is positive voltage and speed command is CW
direction.
Pr43 is 0 (Command pulse inhibition input is valid.), and INH is open.
The position command per each control cycle is 1 pulse or smaller due to,
• No correct entry of command pulse
• No correct connection to the input selected with Pr40.
• No matching to input status selected with Pr41 pr Pr42.
While Pr4E is 0 (Deviation counter clear at level), the deviation counter clear input (CL) is
connected to COM–.
While Pr06 is 1 (Speed zero clamp is valid.), the speed zero clamp input (ZEROSPD) is
open.
While the analog speed command is selected, the analog speed command is smaller than
0.06[V].
While the internal speed command is selected, the internal speed command is set to lower
than 30 [r/min]
The analog torque command input (SPR or CCWTL) is smaller than 5 [%] of the rating.
• While Pr5B is 0 (speed is limited by 4th speed of internal speed), Pr56, (4th speed of
speed setup) is set to lower than 30 [r/min].
• While Pr5B is 1 (speed is limited by SPR input), the analog speed limit input (SPR) is
smaller than 0.06 [V].
The motor runs at 20 [r/min] or lower even though the factors from 1 to 13 are cleared,
(the command is small, the load is heavy, the motor lock or hitting, driver/motor fault etc.)