85
Installation Manual
7-13. Reactive
Power
Mode
Setting
Select the reactive power mode from table listed below
■
Preparation
• See 7-2 and switch to the Parameter Item Selection mode showing the initial display [no4.09].
■
Operation Procedure
• While [no4.09] is displayed, press "MENU (ENTER)" to switch to the Parameter Display mode.
• While the Display mode is selected, press "MENU (ENTER)" to switch to the Parameter Setting mode. Or press
"ON/OFF (CANCEL)" to return to the Parameter Item selection.
• While the Parameter Setting mode is selected and the digit is blinking, press "DATA(▲)" or "CLOCK (▼)" and
select the value from 0 to 4.
• After setting the value, press "MENU (ENTER)" to store the data and switch to the parameter display mode.
Or press "ON/OFF (CANCEL)" to cancel. Then return the Parameter Display mode.
• After returning the Parameter Display mode, press "ON/OFF (CANCEL)" to return the Parameter Item Selection.
Parameter Item
Mode
Explanation
*
0
1
2
3
4
Default Set Point
Australia/New Zealand
Range
Parameter
Selection Display
0
*
0-4
*
Reactive
Power Mode Setteing
Table
Reactive Power Mode
Reactive Power
Mode Setting
Parameter Display Mode
Parameter Item Selection
Parameter Setting Mode
or
or
Characteristic power factor mode only enabled
Fixed power factor mode
only enabled
Fixed reactive power mode only enabled
Volt-var response mode only enabled
All disenable