GTWIN Reference Manual
6.3 GT Series Error Codes
237
Error code
Error
Cause and solution
**1021
Unsupported PLC model
error
The selected PLC model is not supported.
**1022
Password protection error
An incorrect password has been input three times or more.
Turn the power supply off and on again and then input the
correct password.
Upload protection has been turned on for the PLC.
The number of digits was changed when a new password with
the FP monitor function was set. Cancel the password setting
before changing the number of digits.
**1023
Master memory error (FP-X
only)
A master memory has been installed in the FP-X. It is not possible
to transfer programs from an SD memory card to a PLC with the a
master memory.
**1025
General-purpose memory
shortage
There is not enough general-purpose memory available in the
destination PLC.
**1027
Remote mode error
(FP2/FP2SH only)
The PLC is set to RUN mode. Change to REMOTE mode or
PROG. mode.
**102D
Forced operation error
Check whether a device that cannot be forced in PROG. mode
has been forcibly turned on or off.
**1040
The record area for data
logging in the GT was
overwritten
No SD memory card is inserted.
There was an overflow of
the SRAM.
The functions for data logging, line graph and alarm history jointly
use the SRAM.
Transfer all data from GTWIN to avoid the error message.
**1041
The record area for data
logging in the GT was
overwritten
Data cannot be written onto the SD memory card. Check whether
the SD memory card is write-protected.
**1042
The record area for data
logging in the GT was
overwritten
The SD memory card is full.
**1043
SD memory card writing
error
The command to stop writing to the SD card has been sent. Turn
off the command.
**1044
The record area for data
logging in the GT was
overwritten
The command to stop writing to the SD card has been sent. Turn
off the command.
**1045
The record area for data
logging cannot be reserved
in the SRAM
Transfer all data.
**1060
Index register value error
The device value setting for the index modifier is out of range. Set
a value that is in range.
**1080
Start time device value
error
The value set at the start of the line graph function is out of range.
Set a value that is in range.
Setting a value greater than 32 when "no. of plots" is selected will
also result in this error message.
**1100
Ethernet IP address setting
error
The IP address for Ethernet is not specified correctly. Check the
IP address for the GT unit.
**1101
Ethernet subnet mask
setting error
The subnet mask for Ethernet is not specified correctly. Check the
subnet mask for the GT unit.
**1102
Ethernet default gateway
setting error
The default gateway for Ethernet is not specified correctly. Check
the default gateway for the GT unit.
**1103
Ethernet port no. setting
The port no. for Ethernet is not specified correctly. Check the port
Содержание GTWIN
Страница 1: ...TOUCH TERMINALS GTWIN Reference Manual ...
Страница 11: ...Chapter 1 Introducing GTWIN ...
Страница 59: ...Chapter 2 GT Panel System Menu ...
Страница 94: ...Chapter 3 The GTWIN User Interface ...
Страница 108: ...Chapter 4 Menus ...
Страница 182: ...Chapter 5 Parts and Their Functions ...
Страница 234: ...Chapter 6 Troubleshooting ...
Страница 248: ...Chapter 7 Connecting the GT to a PLC ...
Страница 277: ...Connecting the GT to a PLC GTWIN Reference Manual 276 Wiring diagrams For GT with RS485 interface ...
Страница 281: ...Connecting the GT to a PLC GTWIN Reference Manual 280 For GT with RS485 interface and FP X COM4 ...
Страница 286: ...GTWIN Reference Manual 7 13 Connecting Via GT Link 285 Wiring diagrams For GT with RS485 interface and FPG COM3 ...
Страница 287: ...Connecting the GT to a PLC GTWIN Reference Manual 286 For GT with RS485 interface and FPG COM4 ...
Страница 288: ...Chapter 8 SD Card Data Upload from GT to PC ...
Страница 293: ......