Parts and Their Functions
GTWIN Reference Manual
218
Basic Setup tab with default values when "Method to Draw" is "Block"
Basic Setup configuration parameters for block mode
Field
Description
Method to Draw
Block
Number of Lines
Specifies the number of lines.
Note
: In the element setup tab, you still have to define a reference device (starting
address) for each line.
Bar Graph
Select whether to display one or more lines as bar graphs (minimum: 1 line).
Reference Data
Specify whether to display data from a device or logging data from an SD card (see p.
208).
When you select "Device", specify the "Reference Device" on the line settings tab
(see p. 210).
When you select "SD Card", the field "Unit" appears (see p. 211). Specify the time
unit for the logging data.
Unit (only visible when
you activate "SD Card
(Logging Data)"
Note
: see explanation
following table.
1 Year (Month unit)
: Displays the data for 12 months by month in 12 plots. The
graph starts with January.
1 Month (Day unit)
: Displays the data for 31 days by day in 31 plots.
1 Day (Hour unit)
: Displays the data for 24 hours by hour in 24 plots.
Number of Plots
: Specify the desired number of plots on the right side under
"Number of Plots".
You can, for example, display the data for 1 hour beginning with the first value of
the hour and continuing until the number of plots has been reached.
No mathematical calculation can be performed on the data, i.e. no mean, total or
accumulated value.
Direction
Specify in which direction the reference devices sampled are displayed.
Update Device
Specify the device used to trigger updating the line. Subsequent devices trigger
subsequent lines (see "Update Device" at the end of this section).
Use Drawing Complete
Bit
Sets a bit when the graph has been updated (see "Update Device" at the end of this
section).
Содержание GTWIN
Страница 1: ...TOUCH TERMINALS GTWIN Reference Manual ...
Страница 11: ...Chapter 1 Introducing GTWIN ...
Страница 59: ...Chapter 2 GT Panel System Menu ...
Страница 94: ...Chapter 3 The GTWIN User Interface ...
Страница 108: ...Chapter 4 Menus ...
Страница 182: ...Chapter 5 Parts and Their Functions ...
Страница 234: ...Chapter 6 Troubleshooting ...
Страница 248: ...Chapter 7 Connecting the GT to a PLC ...
Страница 277: ...Connecting the GT to a PLC GTWIN Reference Manual 276 Wiring diagrams For GT with RS485 interface ...
Страница 281: ...Connecting the GT to a PLC GTWIN Reference Manual 280 For GT with RS485 interface and FP X COM4 ...
Страница 286: ...GTWIN Reference Manual 7 13 Connecting Via GT Link 285 Wiring diagrams For GT with RS485 interface and FPG COM3 ...
Страница 287: ...Connecting the GT to a PLC GTWIN Reference Manual 286 For GT with RS485 interface and FPG COM4 ...
Страница 288: ...Chapter 8 SD Card Data Upload from GT to PC ...
Страница 293: ......