Parts and Their Functions
GTWIN Reference Manual
206
Tab
Field
Description
Operation
Security
Set the security level to restrict the display and/or operation of the part.
Guidance
No
Specifies whether the guidance text of the alarm list is displayed on the GT
screen.
Display Text
When this is selected, you need to specify the number of lines for the
guidance text as well as the string and the background color.
Display Frame
Sets a frame and its color, if desired.
Display Area
Specifies the number of lines to display. The line width automatically adapts
to fit the longest list entry.
Change Screen
Change to the screen defined in the Screen No. text box.
Color
Specifies the color for the guidance text and its background.
Element
Setup
Language No.
If you work with multiple languages (see p. 159), you can enter alarm texts
for all languages used.
Message
Double-click an alarm message or select [Setup] to enter the text for each
alarm condition.
Guidance
This column is displayed if you have selected "Display Text" on the
"Guidance" tab. Enter the guidance text to be displayed when the
corresponding function switch is pressed.
5.8.3 List of Active Alarms
In this operation mode, the alarm part shows a list of all currently active alarms.
Configuration parameters
What appears on the tabs differs depending on which operation mode you have
selected on the "Basic Setup" tab.
Tab
Field
Description
List
Name
You can assign the configuration settings a name.
Below this field, a list displays the current configuration settings.
Basic Setup
Operation Mode
Active List
: displays a list of active alarms.
History (Time Order)
(see p. 203)
History (Frequency Order)
(see p. 205)
Monitoring
Start Device
: address of the first word of the memory area assigned to the
alarms. The total size of the memory area depends on the number of alarms
set below (minimum 1 word).
Alarm Number
: specifies the number of alarms to be monitored.
Alarm Status
: sets which status of the start device will trigger the alarm.
Color and
Form
Display Area
Number of Lines
: specifies the number of lines (1 to 12) on the base
screen to display alarms. The line width automatically adapts to fit the
longest list entry.
Содержание GTWIN
Страница 1: ...TOUCH TERMINALS GTWIN Reference Manual ...
Страница 11: ...Chapter 1 Introducing GTWIN ...
Страница 59: ...Chapter 2 GT Panel System Menu ...
Страница 94: ...Chapter 3 The GTWIN User Interface ...
Страница 108: ...Chapter 4 Menus ...
Страница 182: ...Chapter 5 Parts and Their Functions ...
Страница 234: ...Chapter 6 Troubleshooting ...
Страница 248: ...Chapter 7 Connecting the GT to a PLC ...
Страница 277: ...Connecting the GT to a PLC GTWIN Reference Manual 276 Wiring diagrams For GT with RS485 interface ...
Страница 281: ...Connecting the GT to a PLC GTWIN Reference Manual 280 For GT with RS485 interface and FP X COM4 ...
Страница 286: ...GTWIN Reference Manual 7 13 Connecting Via GT Link 285 Wiring diagrams For GT with RS485 interface and FPG COM3 ...
Страница 287: ...Connecting the GT to a PLC GTWIN Reference Manual 286 For GT with RS485 interface and FPG COM4 ...
Страница 288: ...Chapter 8 SD Card Data Upload from GT to PC ...
Страница 293: ......