1-12-2-1-1
1
■
Indoor Unit
Type E3
AVOID:
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the performance of the unit.
locations where external air may enter the room directly. This may cause “condensation” on the air discharge ports, causing them to spray
or drip water.
locations where the remote controller will be splashed with water or affected by dampness or humidity.
installing the remote controller behind curtains or furniture.
locations where high-frequency emissions are generated.
places where blocked air passages.
places where the false ceiling is not noticeably on an incline.
DO:
select an appropriate position from which every corner of the room can be uniformly cooled.
select a location where the ceiling is strong enough to support the weight of the unit.
make sure to install protective guards on the suction and discharge side to prevent somebody from touching the fan blades or heat exchanger.
select a location where tubing and drain pipe have the shortest run to the outdoor unit.
allow room for operation and maintenance as well as unrestricted air flow around the unit.
install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length (L) from the outdoor unit
as detailed in the Installation Instructions packed with the outdoor unit.
allow room for mounting the remote controller about 1 m off the floor, in an area that is not in direct sunlight or in the flow of cool air from the
indoor unit.
places where optimum air distribution can be ensured.
places where sufficient clearance for maintenance and service can be ensured.
When transporting the indoor unit to the roof space through the ceiling opening
Transport is possible without separation with
a ceiling opening dimension of over 500 ×
1,150 mm and a roof space dimension as
shown below. After transporting the unit, see
section “HOW TO INSTALL THE INDOOR
UNIT”on page 1-12-2-1-3.
1,000
1,000
1,600
Fan Block
Roof space
Ceiling
Over 1,150
Ceiling opening
Roof space
Unit Block
Unit: mm
It is possible to separate the indoor unit into
Fan Block and Unit Block.
Separated transport if necessary
<Case 1>
If a ceiling opening dimension is over 500
× 1,150 mm and a roof space dimension
is shown below, the indoor unit can be
separated to fit through the space. For
separating procedure, see section “How
to separate the indoor unit”
on page 1-12-2-1-2.
1,500
1,500
900
Ceiling
Over 1,150
Ceiling opening
Roof space
Roof space
Unit Block
Unit: mm
<Case 2>
If a ceiling opening dimension is over 500
× 700 mm and a roof space dimension
is shown below, the indoor unit can be
separated to fit through the space. For
separating procedure, see section “How
to separate the indoor unit”on page
on page 1-12-2-1-2.
1,000
1,000
1,600
Ceiling
Over 700
Ceiling opening
Roof space
Roof space
Unit Block
Unit: mm
Criteria for ceiling opening dimension and
height of roof space
Unit: mm
Width of ceiling
opening
Height of roof
space
Necessity of separating
indoor unit
1,150
1,600
Unnecessary
1,150
900
Necessary
700
1,600
Necessary
1. S-200PE3E5B, S-250PE3E5B
SELECTING THE INSTALLATION SITE
SM830276-00_欧州向け R32シングル TD&SM.indb 1
2019/02/27 11:54:40
Содержание Elite Big PAC-i S-200PE3E5B
Страница 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Страница 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Страница 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Страница 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Страница 197: ...4 15 4 4 3 Outdoor Unit HIC Board U 200PZH2E8 U 250PZH2E8 ACXA73 3104 SM830276 00_ R32 TD SM indb 15 19 02 28 9 01 10...
Страница 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Страница 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...