1-12-2-2-2
1
2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
●
areas where leakage of flammable gas may be expected.
●
places where large amounts of oil mist exist.
●
direct sunlight.
●
locations near heat sources which may affect the
performance of the unit.
●
locations where external air may enter the room directly.
This may cause “condensation” on the air discharge ports,
causing them to spray or drip water.
●
locations where the remote controller will be splashed with
water or affected by dampness or humidity.
●
installing the remote controller behind curtains or furniture.
●
locations where high-frequency emissions are generated.
DO:
●
select an appropriate position from which every corner of the
room can be uniformly cooled.
●
select a location where the ceiling is strong enough to
support the weight of the unit.
●
select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
●
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
●
the limitation of the tubing length between the indoor and
the outdoor units should be referred to the Installation
Instructions of the outdoor unit.
●
allow room for mounting the remote controller about 1 m off
the floor, in an area that is not in direct sunlight or in the flow
of cool air from the indoor unit.
4-Way Cassette Type
W
all
indoor unit
indoor unit
min. 1 m
min.
1 m
Ov
er 2.5 m
min. 3 m
Obstacles
Ceiling
1 m
1 m
1 m
1 m
281258_EU.indb 7
2016-9-1 13:03:39
3. HOW TO INSTALL THE INDOOR UNIT
Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to check
that the unit is level.
Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using
the method shown in the diagrams, by attaching them
to the ceiling support structure, or by any other method
that ensures that the unit will be securely and safely
suspended.
Note: For DC Fan Tap Change Procedure for 4-Way
Cassette, see page
1
-12-2-2-13.
Hole-in-anchor
Hole-in-plug
Concrete
Insert
Suspension bolt
(M10 or 3/8")
(field supply)
Drain outlet (other side)
(VP25)
Suspension lug
* Over 20 mm
* Over 20 mm
340 mm
840 mm
950 mm
272 mm
50 mm
Refrigerant tubing joint (liquid side)
Refrigerant tubing joint (gas side)
184 mm
134 mm
33.5 mm
177 mm
Type 100 ~ 1
25
: 319 mm
127 mm
Indoor Unit
View from top
A:
700 mm
A: 780 mm
B: 860 ~ 910 mm
A: (suspension bolt pitch)
B: (ceiling opening dimension)
B:
860 ~ 910 mm
(2) Follow the diagram to make the holes in the ceiling.
(3) Determine the pitch of the suspension bolts using the supplied full-scale installation diagram (printed on container box).
The diagram show the relationship between the positions of the suspension fitting, unit, and panel.
Use the nut (field supply) and washer (supplied) for upper and lower position of the suspension lug.
* The overlapping portion between the ceiling and panel for cassette should be kept over 20 mm.
281258_EU.indb 8
2016-9-1 13:03:40
Type 50 ~ 71:256mm
2016-9-1 13:03:40
281258_EU.indb 8
2016-9-1 13:03:40
HOW TO INSTALL THE INDOOR UNIT
SM830276-00_欧州向け R32シングル TD&SM.indb 2
2019/02/27 11:54:51
Содержание Elite Big PAC-i S-200PE3E5B
Страница 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Страница 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Страница 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Страница 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Страница 197: ...4 15 4 4 3 Outdoor Unit HIC Board U 200PZH2E8 U 250PZH2E8 ACXA73 3104 SM830276 00_ R32 TD SM indb 15 19 02 28 9 01 10...
Страница 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Страница 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...