6-12
6
6
Never use the DN code unlisted in the following table.
(P) : Factory preset mode
DN
Item
Setting No.
05 Outdoor fan silent mode
1=Silent mode 1 (P)
2=Silent mode 2,,,,, 3=Silent mode 3
07 Capacity matching ignored
0=Invalid (P)
1=Valid
0C Indoor unit drain pump forced operation
0=Invalid
1=stop for 2 hours and drive for 20 minutes constantly
2=stop for 20 minutes and drive for 20 minutes constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
0D Measures against smell when indoor unit cooling
thermostat OFF
0=Invalid (P)
1=Measures against smell
1A Demand 1 current (%)
0=0%
40=40%
45=45%,,,,,
75=75% (P) ,,,,,
130=130%
-1=No control
1B Demand 2 current (%)
0=0%
40=40%
45=45%,,,,,
50=50% (P) ,,,,,
130=130%
-1=No control
1D Current control level
0=40%
1=45%,,,,,
12=100%,,,,,
16=120%,,,,,
18=130,,,,,
19=-1(Invalid)(P)
2B DP operation time for slime measures
20=20 minutes
30=30 minutes (P)
40=40 minutes
50=50 minutes
60=60 minutes
80 Refrigerant Type
410=R410A(P), 22=R22, 407=R407C, 32=R32
81
Outdoor unit capacity
(Setting when the data is not stored in the EEPROM.
Do not change under normal conditions.)
0=Invalid
224 (Type 200)
280 (Type 250)
SM830276-00_欧州向け R32シングル TD&SM.indb 12
19/02/12 15:38:58
Содержание Elite Big PAC-i S-200PE3E5B
Страница 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Страница 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Страница 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Страница 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Страница 197: ...4 15 4 4 3 Outdoor Unit HIC Board U 200PZH2E8 U 250PZH2E8 ACXA73 3104 SM830276 00_ R32 TD SM indb 15 19 02 28 9 01 10...
Страница 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Страница 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...