1-12-2-2-26
1
ECONAVI SYSTEM SETTING
Change the settings of main and sub indoor units to
correspond to the ECONAVI system function.
For the benefit of using the ECONAVI function, the main
indoor unit should be provided with the ECONAVI function.
1. Press three buttons.
Keep pressing the
,
and
buttons
simultaneously for more than 4 seconds.
The “Maintenance func” menu appears on the screen.
2.
Select “0. ECONAVI info.” from the menu command.
By pressing the
/
buttons, select
“0. ECONAVI info.” and press the
button.
3.
Select “System settings” from the menu command.
By pressing the
/
buttons, select
“System settings” and press the
button.
4.
Start settings.
By pressing the
/
buttons, select “YES” and
press the
button.
5.
When finished settings, the system restarts automatically.
6.
Check whether the ECONAVI function is set.
is displayed on the screen.
If the display is not operated, press the
button
and set it in operating mode.
If operation is in fan mode,
is not
displayed. Set in any operating mode other than fan
mode.
“
” is displayed when
setting the ECONAVI function.
NOTE
After operating Step 2, the following messages may occasionally appear on the screen.
Display message
Contents
Disabled in default mode.
After a while, select “0. ECONAVI info.” again.
If no status changes even after 10 minutes, make auto address setting and then
select “0. ECONAVI info.”.
After operating Step 3, the following messages may occasionally appear on the screen.
Display message
Contents
Setup is not required.
The main indoor unit has already been provided with the ECONAVI function.
So, it works right out of the box.
Main indoor unit is not found.
The power of indoor unit may possibly shut down.
Check the power supply of indoor unit.
Indoor unit with ECONAVI is not found.
Since all indoor units in the group control are not available for the ECONAVI
function, the ECONAVI function cannot be used.
ECONAVI TEST OPERATION
Preparation: Refer to the manuals of the indoor unit and turn
on the main power switch in advance.
Human detection cannot be made for approx.
90 seconds when switched on the power
because the human detection sensor is set in
initial setup.
1. Press three buttons.
Keep pressing the
,
and
buttons
simultaneously for more than 4 seconds.
The “Maintenance func” menu appears on the screen.
2.
Select “0. ECONAVI info.” from the menu command.
By pressing the
/
buttons, select
“0. ECONAVI info.” and press the
button.
3.
Select “Error found” from the menu command.
By pressing the
/
buttons, select “Error
found” and press the
button.
4.
Check the sensor status shows “Normal”.
(By pressing the
/
buttons, the status of
each indoor unit can be scrolled on the screen.)
The sensor status of all indoor units are displayed.
•
“Normal”: The sensor on the panel for cassette
(ECONAVI type) works normally.
•
“Preparing”: The sensor on the panel for cassette
(ECONAVI type) is set in initial setup.
Confirm that “Normal” appears within 90 seconds.
•
“Unsupported”: Indoor units not available for ECONAVI
function.
The test run procedure described above is over. If any
display appears other than “Normal” or “Preparing” even
though the ECONAVI panel is connected, follow the Step 5
below.
* “1-1”, “1-2” mean indoor unit No. If the indoor unit is without
ECONAVI panel, “Not connected” appears.
* “Sensor 1” means optional ECONAVI sensor
(CZ-CENSC1). If not connected, “Not connected” appears
besides “Sensor 1” on the screen.
5.
If the sensor status shows other than “Normal”,
“Preparing”,
If the sensor status shows “Error” or “Not connected”
although the panel for cassette (ECONAVI type) is
connected, the following symptom may have occurred.
Specify the applicable indoor unit and check the sensor.
“Error”: The sensor may possibly be damaged.
”Not connected”: The wiring between the indoor unit and
sensor may possibly be disconnected.
* The specified indoor unit can be confirmed by the flap
operation.
Confirmation method:
1
Finish the maintenance function.
Press the
button to show the maintenance
function display and then press the
button.
2
Operate the flap.
By pressing the
button, select the applicable
“Indoor Unit No.” in the list of “2. FLAP” and then
make flap setting. The indoor unit which responds to
the flap setting becomes available.
When the indoor unit is specified, turn off the main
power switch and disconnect the connector of sensor
wiring from the PCB. Then reconnect it. Turn on the
main power switch and repeat the Steps 1 to 4 described
above. Confirm the display shows “Error found”. If the
display shows “Error” or “Not connected” on the screen
again, it is necessary to replace the panel for cassette
(ECONAVI type) with a new one.
SM830276-00_欧州向け R32シングル TD&SM.indb 26
2019/02/27 11:55:16
Содержание Elite Big PAC-i S-200PE3E5B
Страница 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Страница 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Страница 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Страница 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Страница 197: ...4 15 4 4 3 Outdoor Unit HIC Board U 200PZH2E8 U 250PZH2E8 ACXA73 3104 SM830276 00_ R32 TD SM indb 15 19 02 28 9 01 10...
Страница 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Страница 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...