2
2
2-4
CZ-RTC5B (High-spec wired remote controller)
Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Press the
or
button to see each menu.
If you wish to see the next screen instantly, press the
or
button.
Select “4. Test run” on the LCD display and press the
button.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Change the display from OFF to ON by pressing the
or
button. Then press the
button.
[
] Confirm
Test run
Change
20:30 (THU)
Test run
ON
Press the
button. “TEST” will be displayed on the
LCD display.
TEST
START
[
]
20:30 (THU)
Press the
button. Test run will be started.
Test run setting mode screen appears on the LCD
display.
TEST
20:30 (THU)
COOL
MODE
START
[
]
20:30 (THU)
CZ-RTC5B
CZ-RTC4 (Timer remote controller)
(1)
(2)
(3)
(4)
Press the remote controller
button for 4 seconds or longer.
Then press the
button.
“
” appears on the LCD display while the test run is in progress.
The temperature cannot be adjusted when in Test Run mode.
(This mode places a heavy load on the machines.
Therefore use it only when performing the test run.)
The test run can be performed using the HEAT, COOL, or FAN
operation modes.
NOTE
The outdoor units will not operate for approximately 3 minutes after the
power is turned ON and after operation is stopped.
If correct operation is not possible, a code is displayed on the remote
controller LCD display.
(See the section “7. Self-Diagnostic Function Table and Contents of
Alarm Display” and correct the problem.)
After the test run is completed, press the
button again.
Check that “
” disappears from the LCD display.
(To prevent continuous test runs, this remote controller includes a timer
function that cancels the test run after 60 minutes.)
* If the test run is performed using the wired remote controller, operation
is possible even if the cassette-type ceiling panel has not been
installed. (“P09” display does not occur.)
CZ-RTC4
(1)
(2)
(3)
(4)
(1)
(1)
(4)
2-4. Test Run Procedure
Indoor Units
2-3. Caution
The indoor and outdoor unit control PCB utilizes a semiconductor memory element (EEPROM).
The settings required for operation were made at the time of shipment.
Only the correct combinations of indoor and outdoor units can be used.
This test run section describes primarily the procedure when using the wired remote controller.
Fig. 2-5
YES
YES
YES
NO
NO
NO
Recheck the items to check before the test run.
Check the combination (wiring) of indoor and outdoor units.
(See 2-8-1)
(See 2-5)
Is system “single-type”?
(1 indoor unit is connected to 1 outdoor unit
and remote controller)
Is group control with
multiple outdoor units used?
Turn ON the indoor and outdoor power.
Indicate (mark) the combination number.
(See 2-8-3)
Automatic address
Set the remote controller to “test run”.
(See 2-6)
Can
operation be
started?
Return the remote controller to normal control.
Turn ON the indoor
and outdoor power.
(Automatic
Address)
(See 2-8-2)
Setting the Outdoor
Unit System Address
Set the outdoor
unit system address.
(See 2-8-3)
Automatic Address Setting
Use the remote controller
to perform automatic
address setting.
See “Contents of Remote
Controller Switch Alarm Display”
to check the system.
In addition, see 2-8-1 to 4 and
correct any items that need to be
corrected.
Note: Check the indoor-side drainage.
(*1) Required for simultaneous-operation
multi systems and for group control.
(*1)
SM830276-00_欧州向け R32シングル TD&SM.indb 4
19/02/28 13:22:57
Содержание Elite Big PAC-i S-200PE3E5B
Страница 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Страница 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Страница 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Страница 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Страница 197: ...4 15 4 4 3 Outdoor Unit HIC Board U 200PZH2E8 U 250PZH2E8 ACXA73 3104 SM830276 00_ R32 TD SM indb 15 19 02 28 9 01 10...
Страница 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Страница 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...