vi
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
(1) Process tubing
Material: Use seamless phosphorous deoxidized copper tube for refrigeration. Wall thickness shall comply with the applicable legislation. For tubes of ø22.22 or
larger, use the
material of temper 1/2H or H (Hard copper tube). Do not bend the hard copper tube.
For the renewal tubing size, refer to the Technical Data.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
CAUTION
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to prevent dirt, moisture, or other foreign
substances from entering. These substances can result in system malfunction.
(2) Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R32 refrigerant deterioration and compressor defects. Due to
the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
(1) Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining refrigerant and recharge the required total amount of
new refriger
ant after fixing the leak.
3. Different tools required
(1) T
ool specifications h
ave been changed due to the characteristics of R32.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
Item
Different tools?
(From R22 and R407C)
R410A tools
compatible with R32?
Remarks
Manifold gauge
Yes
Yes
Types of refrigerant, refrigerating machine oil, and
pressure gauge are different.
Charge hose
Yes
Yes
To resist higher pressure, material must be changed.
Vacuum pump
Yes
Yes
Use a conventional vacuum pump if it is equipped
with a check valve. If it has no check valve, purchase
and attach a vacuum pump adapter.
Leak detector
Yes
Yes
Leak detectors for CFC and HCFC that react to
chlorine do not function because R32 and R410A
contains no chlorine. Leak detectors for HFC can be
used for R32 and R410A.
Flaring oil
Yes
Yes
For systems that use R22, apply mineral oil (Suniso
oil) to the flare nuts on the tubing to prevent
refrigerant leakage. For machines that use R32 or
R410A, apply synthetic oil (ether oil) to the flare nuts.
* Using tools for R22 and R407C can cause defects.
Manifold gauge
Vacuum pump
Outlet
Inlet
Single-outlet valve
(with siphon tube)
Liquid refrigerant should be recharged with
the cylinder standing on end as shown.
Valve
Liquid
SM830276-00_欧州向け R32シングル TD&SM.indb 7
19/02/26 15:26:21
Содержание Elite Big PAC-i S-200PE3E5B
Страница 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Страница 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Страница 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Страница 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Страница 197: ...4 15 4 4 3 Outdoor Unit HIC Board U 200PZH2E8 U 250PZH2E8 ACXA73 3104 SM830276 00_ R32 TD SM indb 15 19 02 28 9 01 10...
Страница 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Страница 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...