2
2
2-3
2-2. Precautions
Request that the customer be present when the test run is performed.
At this time, explain the operation manual and have the customer perform the actual steps.
Be sure to pass the manuals and warranty certificate to the customer.
Check that the 220 – 240 VAC power is not connected to the inter-unit control wiring connector terminal.
* If 220 – 240 VAC is accidentally applied, the indoor or outdoor unit control PCB fuse will blow in order to
protect the PCB.
Correct the wiring connections, then disconnect the 2P
connectors that are connected to the PCB, and replace
them with 2P connectors.
If operation is still not possible after changing the brown
connectors, try cutting the varistor.
(Be sure to turn the power OFF before performing
this work.)
Fig. 2-3
Check that the 220 –240 VAC power is not connected to
the inter-unit control wiring connector terminal.
* If 220 –240 VAC is accidentally applied, the indoor unit
control PCB fuse will blow in order to protect the PCB.
In this case, make the wiring correctly.
Then disconnect the 2P connectors (OC) that are
connected to the indoor unit PCB, and replace them
with 2P connectors (EMG).
If operation is still not possible after changing the brown
connectors, cut the jumper on the indoor unit PCB.
(Be sure to turn the power OFF before performing this
work.)
Fig. 2-4
OC (CN040, blue)
EMG (CN044, brown)
Jumper
(JP040)
OUTDOOR UNIT MAIN PCB (CR)
INDOOR UNIT MAIN PCB (CR)
Outdoor main PCB
LED1
CHK pin
PUMPDOWN
RUN pin
MODE pin
*MODE pin: factory setting is cooling operation
mode.
LED2
SM830276-00_欧州向け R32シングル TD&SM.indb 3
19/02/28 13:22:57
Содержание Elite Big PAC-i S-200PE3E5B
Страница 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Страница 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Страница 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Страница 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Страница 197: ...4 15 4 4 3 Outdoor Unit HIC Board U 200PZH2E8 U 250PZH2E8 ACXA73 3104 SM830276 00_ R32 TD SM indb 15 19 02 28 9 01 10...
Страница 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Страница 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...