1-12-1-1-7
1
Check of Density Limit
U-200PZH2E8, U-250PZH2E8
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for installation space of
appliance are determined according to the refrigerant charge amount [m
c
] used in the appliance.
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows:
[m
c
] : The refrigerant charge amount (Total of refrigerant at shipment and refrigerant charge amount in the field).
[m
max
] : Maximum refrigerant charge amount
[m
c
] ≤ 1.22 : Can be installed
1.22 < [m
c
] ≤ [m
max
] : Installation possible with in the range of slanted line part
[m
c
] > [m
max
] : Can not be installed
0.0
5.0
1
0.0
1
5.0
20.0
25.0
30.0
35.0
40.0
45.0
0.0 0.5
1
.0
1
.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5
7.80
1.22
[Amin]
: mini
m
um indoor floor space (m
2
)
[m
c
] : the refrigerant charge amount (k
g
)
Can be installed
Can not be installed
• 7.80 indicates m
max
digit of the model U-200PZH2E8, U-250PZH2E8.
U-200PZH2E8
U-250PZH2E8
m
max
7.80 k
g
SM830276-00_欧州向け R32シングル TD&SM.indb 7
2019/02/27 11:54:26
Содержание Elite Big PAC-i S-200PE3E5B
Страница 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Страница 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Страница 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Страница 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Страница 197: ...4 15 4 4 3 Outdoor Unit HIC Board U 200PZH2E8 U 250PZH2E8 ACXA73 3104 SM830276 00_ R32 TD SM indb 15 19 02 28 9 01 10...
Страница 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Страница 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...