6-11
6
6
6-6. Settings Modes: Setting the Outdoor Unit EEPROM
Setting mode 1
<Operating procedure>
2WAY SYSTEM
Outdoor Unit Maintenance Remote Controller
6. Mode Settings
Press and hold the
(1)
(2)
(Check) button and
(Ventilation) button simultaneously for 4
seconds or longer.
Press the temperature setting
and
buttons to change the item code. The item codes
and setting data are shown on the next page.
Press the timer time
buttons to
change the setting data.
To confirm the changed setting data, press the
button.
(At this time, “ ” display stops blinking
and remains lit.)
During this mode, “ ” is displayed,
blinking. The outdoor unit address display section
displays “ALL,” the item code and number (DN
value in the table), and the setting data (6 digits).
(The setting data is displayed in 6 digits. The
display changes between the first 3 digits (Fig. (C)).
and the last 3 digits (Fig. (D)).
(D)
(C) and (D) are displayed alternately.
(C)
When the first 3 digits are displayed, the bottom dot
of the colon is illuminated.)
To exit the setting mode, press the
(Check)
button.
(2)
(5)
(1)
(Example shows display of 000 001.)
Display of fi rst 3 digits
Display of last 3 digits
(3)
(4)
(5)
and
(3)
(2)
(5)
(1)
(3)
A
A
SM830276-00_欧州向け R32シングル TD&SM.indb 11
19/02/12 15:38:58
Содержание Elite Big PAC-i S-200PE3E5B
Страница 12: ...MEMO Xi SM830276 00_ R32 TD SM indb 12 19 02 26 15 26 22...
Страница 160: ...1 14 8 MEMO SM830276 00_ R32 TD SM indb 8 2019 02 27 11 55 39...
Страница 176: ...MEMO 2 16 SM830276 00_ R32 TD SM indb 16 19 02 28 13 23 00...
Страница 182: ...MEMO 3 6 SM830276 00_ R32 TD SM indb 6 19 02 26 10 39 17...
Страница 197: ...4 15 4 4 3 Outdoor Unit HIC Board U 200PZH2E8 U 250PZH2E8 ACXA73 3104 SM830276 00_ R32 TD SM indb 15 19 02 28 9 01 10...
Страница 238: ...MEMO 5 38 SM830276 00_ R32 TD SM indb 38 19 02 28 13 29 52...
Страница 316: ...201903 SM830276 00_ R32 TD SM indb 1 19 02 15 8 52 12...